User Guide Gamatronic Electronic Industries Ltd.
µ
PS-SP 3:3, 3x220 in, 3x208 60 Hz out
Installation
50
9.
Press UPS ON, and wait 60 seconds before
proceeding to the next step.
While you are waiting, the UPS turns on the
Inverter, then checks the Bypass voltage.
If the Bypass voltage is acceptable the UPS
connects the Bypass voltage to the output terminal.
The unit then begins to construct the Inverter
voltage, after which time it transfers to Inverter
mode.
10.
Check the LED indicators to verify that the
UPS is now in Inverter mode.
“B/P” LED is OFF
”INV” LED is GREEN
11.
The UPS executes an automatic battery test for 1 minute.
12.
Verify that the message “UPS OK” appears on the LCD display, and
that NO RED LED is lit
13.
Turn ON the UPS Output circuit breaker.
14.
Measure to insure that the following voltages are present at the UPS
output terminal:
BETWEEN VOLTAGE
R and S
S and T
T and R
208V ±2%
15.
The UPS is ready for use and begins charging the batteries. Connect the
equipment to be protected by the UPS and verify that it is functioning
correctly.