Service / special operation
Burner hours interval
(7040)
Setting of the interval for maintenance of the burner.
Burn hrs since maintenance
(7041)
Burner hours since the last maintenance.
Note
: The burner hours are only counted, when the maintenance message has be-
en activated.
Burner start interval
(7042)
Setting of the interval for burner starts for maintenance.
Burn starts since maint
(7043)
Burner starts since the last maintenance.
Note
: The burner starts are only counted, when the maintenance message has be-
en activated.
Maintenance interval
(7044)
Setting of maintenance interval in months.
Time since maintenance
(7045)
Passed time since the last maintenance interval.
Note
: The time is only counted, when the maintenance message has been activa-
ted.
Fan speed ionization current
(7050)
Speed limit from which the ionisation current service alarm should be set (prog.
no. 7051), if the ionisation current monitoring and therefore a speed increase ba-
sed on too low ionisation current active is.
Message ionization current
(7051)
Function for display and reset of the burner ionisation current service alarm. The
service alarm can only be reset if the reason for service is taken care of.
Chimney-sweep function
(7130)
The chimney sweep function is switched on or off under this prog no.
Note
:
The function is switched off by the setting "Off" or automatically if the maximum
boiler temperature is reached.
It can also be directly activated via the chimney sweep button.
Manual control
(7140)
Activation of manual control. If the manual control function is activated the boi-
ler will be controlled to the Setpoint manual control. All pumps will be activated.
Additional request will be ignored!
Controller stop function
(7143)
If the controller stop function is activated, the burner output set in the setpoint
controller stop is immediately requested by the device.
Controller stop setpoint
(7145)
With activated controller stop function the output set here is requested by the
device.
Telephone customer service
(7170)
Here the desired telephone number of customer service can be entered.
PStick storage pos
(7250)
Via the parameter
PStick Storage Pos
the data set (data set number on the stick)
can be selected which should be written or read.
Programming
358 488 09.10
Gas-fired fuel value boiler EuroCondense three 125-300 kW
73