Function
Prog.
no.
Level
1)
Standard value
With buffer
No | Yes
5090
E
Yes
With prim contr/system pump
No | Yes
5092
E
Yes
With solar integration
No | Yes
5093
E
Yes
Pump speed min
5101
E
0%
Pump speed max
5102
E
100%
Speed Xp
5103
E
35°C
Speed Tn
5104
E
120 s
Speed Tv
5105
E
45 s
Transfer strategy
Always | DHW release
5130
E
Always
Interm circ boost recharging
5139
E
5°C
Intermediate circuit boost
5140
E
3°C
Excess interm circ temp max
5141
E
2°C
Flow setp compensation delay
5142
E
30 s
Flow setp compensation Xp
5143
E
60°C
Flow setp compensation Tn
5144
E
30 s
Flow setp compensation Tv
5145
E
30 s
Full charging with B36
No | Yes
5146
E
Yes
Min start temp diff Q33
5148
E
-3°C
Excess interm circ temp del
5151
E
30 s
Configuration
Heating circuit 1
Off | On
5710
C
ON
Heating circuit 2
Off | On
5715
C
Off
Heating circuit 3
Off | On
5721
C
Off
DHW sensor
DHW sensor B3 | Thermostat
5730
E
DHW sensor B3
DHW controlling element Q3
No charging request | Charging pump | Diverting valve
5731
E
Charging pump
Basic pos DHW div valve
Last request | Heating circuit | DHW
5734
E
Last request
DHW separate circuit
Off | On
5736
E
Off
Optg action DHW div valve
Position on DHW | Position on heating circuit
5737
E
Position on DHW
Ctrl boiler pump/DHW valve
All requests | Request HC1/DHW only
5774
E
All requests
Solar controlling element
Charging pump | Diverting valve
5840
E
Charging pump
Programming
20
Gas-fired fuel value boiler EuroCondense three 125-300 kW
358 488 09.10
Summary of Contents for Eurocondense three
Page 117: ...Space for notes 358 488 09 10 Gas fired fuel value boiler EuroCondense three 125 300 kW 117 ...
Page 118: ...Space for notes 118 Gas fired fuel value boiler EuroCondense three 125 300 kW 358 488 09 10 ...
Page 119: ...Space for notes 358 488 09 10 Gas fired fuel value boiler EuroCondense three 125 300 kW 119 ...