Operator section save basic
settings
(30)
The data of the control will be written into the room unit (only available for room
unit).
Caution!
The data of the room unit will be overwritten! With this, the individual
programming of the control in the room unit can be ensured.
Operator section activate
basic settings
(31)
The data of the operating unit or room unit will be written into the control.
Caution!
The data of the control will be overwritten! The factory settings are sto-
red in the operating unit.
- Activation of the prog. no. 31 at the
operating unit
:
The control will be reset to the
factory settings.
- Activation of the prog. no. 31 at the
room device
:
The individual programming of the room unit will be written into the control.
Use as
(40)
-
room device 1/2
: this setting establishes which heating circuit the room unit on
which this setting is made should be used. When selecting
room unit 1
the
room device can be assigned to more heating circuits using prog. no. 42, while
with the selection of
room unit 2
only heating circuit 2 can be controlled.
-
Operator unit
: this setting is provided for the pure operation without room
functions and is not needed in connection with this controller.
-
service unit
: this setting is used, for example, to secure or save control settings.
Attribution room device 1
(42)
If the setting
room unit 1
(prog. no. 40) is selected on the room unit, it must be
specified on prog. no. 42 whether the room unit of heating circuit 1 or both hea-
ting circuits will be assigned.
Operation HC2/HC3/P
(44, 46)
When selecting
room device 1
or
operating unit
(prog.no. 40), it must be set un-
der program number 44 or 46, if the heating circuits HC2 and HC3/P have to be
operated together with heating circuit 1 or independent from heating circuit 1 by
the operator unit.
Effect of presence button
(48)
The effect of the presence button on the heating circuits has to be set under pro-
gram number 48.
Readjustment room sensor
(54)
The temperature display of the value, transmitted by the room sensor, can be cor-
rected under programme no. 54.
Software version
(70)
Display of the current software version.
Radio
Detailed descriptions are in the assembly and setting manual of the room device
RGTF.
Device lists
(130 to 138)
The state of the respective device will be displayed under programme numbers
130 to 138.
Programming
358 488 09.10
Gas-fired fuel value boiler EuroCondense three 125-300 kW
33