Floor curing function
(850, 1150)
The floor curing function serves controlled drying out of screed floors
-
Off
: the function is switched off.
-
Functional heating
(Fh): Part 1 of the temperature profile will be run through
automatically.
-
Curing heating
(Bh): Part 2 of the temperature profile will be run through auto-
matically.
-
Functional heating and curing heating
: The whole temperature profile will be
run through automatically.
-
Manual
: Control to the floor curing setpoint manually.
Fig. 8: Temperature profile of the floor -curing function
[day]
x
Fh
Ch
Fh+Ch
X
Starting day
Fh Functional heating
Ch Curing heating
Important!
The respective regulations and standards of the screed manufacturer
have to be observed.
A correct function is only possible with a correctly installed plant (hydraulic, elect-
rical systems and settings).
Deviations can only lead to damage of the screed.
The floor curing function can be stopped prematurely by setting
0=OFF
.
Floor curing setp manually
(851, 1151, 1451)
Setting of temperature, up to which manual control is carried out at activated
floor curing function (see prog. no. 850).
Screed nominal value actual
(1455)
Display of the current floor curing setpoint.
Screed day actual
(856, 1156, 1456)
Display of the current day of the floor curing function.
Programming
42
Gas-fired fuel value boiler EuroCondense three 125-300 kW
358 488 09.10