Function
Prog.
no.
Level
1)
Standard value
Temp differential nominal
2317
C
10°C
Pump modulation
None | Demand | Boiler setpoint | Temp differential nominal | Burner
output
2320
E
Demand
Pump speed min
2322
E
0 %
Pump speed max
2323
E
100 %
Output nominal
2330
E
50 kW
Output basic stage
2331
E
30 kW
Output at pump speed min
2334
E
0 %
Output at pump speed max
2335
E
100 %
Max fan output heating operation
2441
E
0 kW
Max fan output heating full charging
2442
E
0 kW
Fan output DHW max.
2444
E
0 kW
Fan shutdown heating mode
Off | On
2445
E
Off
Fan shutdown delay
2446
E
3 s
Controller delay
Off | Heating mode only | DHW mode only | Heating and DHW mode
2450
E
Heating mode only
Fan output controller delay
2452
E
0 kW
Control delay duration
2453
E
10 s
Switching diff on HCs
2454
E
4°C
Switching diff off min HCs
2455
E
5°C
Switching diff off max HCs
2456
E
7°C
Switching diff on DHW
2460
E
5°C
Switching diff off min DHW
2461
E
6°C
Switching diff off max DHW
2462
E
8°C
Pressure switch shutdown
Start prevention | Lockout position
2500
E
Lockout position
Cascade
Lead strategy
Late on, early off | Late on, late off | Early on, late off
3510
E
Late on, late off
Release integral source seq
3530
E
50°C*min
Reset integral source seq
3531
E
20°C*min
Restart lock
3532
E
300 s
Switch on delay
3533
E
5 min
Auto source seq ch'over
3540
E
500 h
Auto source seq exclusion
None | First | Last | First and last
3541
E
None
Leading source
Source 1 | Source 2 | Source 3 | Source 4 | Source 5 | Source 6 | Source 7
| Source 8 | Source 9 | Source 10 | Source 11 | Source 12 | Source 13 |
Source 14 | Source 15 | Source 16
3544
E
Source 1
Return setpoint min
3560
E
8°C
Temp differential min
3590
E
- - -°C
Solar
Programming
358 488 09.10
Gas-fired fuel value boiler EuroCondense three 125-300 kW
17