Function
Prog.
no.
Level
1)
Standard value
With buffer storage tank
No | Yes
1928
E
Yes
With prim contr/system pump
No | Yes
1930
E
Yes
Swimming pool circuit
Flow temp setp cons request
1959
C
70°C
DHW charging priority
No | Yes
1974
E
Yes
Excess heat draw
Off | On
1975
E
ON
With buffer storage tank
No | Yes
1978
E
Yes
With prim contr/system pump
No | Yes
1980
E
Yes
Swimming pool
Setpoint solar heating
2055
Eu
26°C
Setpoint source heating
2056
Eu
22°C
Charging priority solar
No | Yes
2065
E
No
Swimming pool temp max
2070
E
32°C
With solar integration
No | Yes
2080
E
Yes
Primary contr/system pump
Flow temp setpoint min
2110
F
8°C
Flow temp setpoint max
2111
F
80°C
Syst pump on heat gen lock
Off | On
2121
F
Off
Mixing valve boost
2130
F
10°C
Actuator running time
2134
F
120 s
Primary contr/system pump
Before buffer | After buffer
2150
F
After buffer
Boiler
Setpoint min
2210
E
40°C
Setpoint max
2212
E
80°C
Setpoint manual control
2214
Eu
60°C
Burner running time min
2241
E
0 min
Burner running time min
2243
E
0 min
SD burner off time
2245
E
15°C
Pump overrun time
2250
E
5 min
Pump overr time after DHW
2253
E
1 min
Boiler pump on heat gen lock
Off | On
2301
E
Off
Impact heat generation lock
Heating mode only | Heating and DHW mode
2305
E
Heating mode only
Temp differential max
2316
C
20°C
Programming
16
Gas-fired fuel value boiler EuroCondense three 125-300 kW