6-106
PFC-6800 • 5403602 • Rev B • 2/13
Cabinet Wiring Connections
PSN-1000 Wiring
Figure 149.
Rechargeable Battery Circuit
The battery charging circuit is on the power supply board providing terminal connections to connect the wire leads. The battery
must be a recognized or listed sealed lead acid battery or equivalent.
The battery circuit is rated for 8 to 55 AH batteries and will operate the panel alarm for at least 24 hours and 5 minutes. The
cabinet will house up to two (2) 18 AH batteries.
The battery charging voltage is approximately 27.3 vDC and the circuit is supervised. The maximum battery charging circuit is
1.0 amp DC.
Battery Circuit Calculation
Before selecting the battery, the installer
must
determine the minimum size batteries for standby and alarm times desired for each
application's current draw.
If the wrong batteries are installed or incorrect current draw used, the proper standby and minimum
alarm time will not be present.
Please use the
Battery Calculation Worksheet
included in this section to calculate the battery size and current draw required for
each application.
120VAC 50Hz-60Hz
240VAC 50Hz-60Hz
Connect to separate
unswitched AC circuit
DWG #602-23
Power limited
wiring
P-Link
Terminals
Non-power limited
relay connection
Non-power limited
battery connection