![Potter PFC-6800 Installation, Operation, & Programming Manual Download Page 11](http://html1.mh-extra.com/html/potter/pfc-6800/pfc-6800_installation-operation-and-programming-manual_1582899011.webp)
2-5
PFC-6800 • 5403602 • Rev B • 2/13
Electrical Specifications
Please refer to the table below for electrical specifications:
System Panel Electrical Specifications
Table 3:
Panel
# NACs
Rating
per NAC
I/O Circuits
(As Outputs)
SLC Power
Notes
Style and Class
PFC-6800
6 up to 10 if
all I/O circuits
configured as
NACs
3 Amp
1 Amp
Maximum Load
of 56.055 mA
One built-in SLC
Loop, up to 7
additional using
SLCE-127s
SLC – Class A or B
NAC – Class A or B
P-Link – Class A or B
I/O – Class B only
All are Low voltage
and Power Limited
System Size Specifications
Please refer to the table below for system size specifications:
System Size Specifications
Table 4:
Accessories/Subassemblies
Maximum System Size
PFC-6800
One (1) built-in SLC Loop with 127 addressable points
•y
Up to seven (7) additional loops using SLCe-127 loop expanders
•y
Six (6) notification circuits on the main board
•y
Four (4) I/O circuits
•y
UD-1000
One (1) DACT