3-43
PFC-6800 • 5403602 • Rev B • 2/13
SLCE-127 Board Shown Installed in PFC-6800 Cabinet
Figure 54.
P-Link Circuit
The P-Link terminals are located in the lower left portion of the circuit board as shown in the figure below. These are low voltage
power limited connections. All P-Link wiring connections are fully supervised.
Setting Addresses
The SLCe's address is set by
dip switch S1
(
as shown below
). The address must be set in the range of one to thirty-one (1–31) to
be recognized by the panel.
(Refer to the "P-Link Addresses" table shown earlier in this section for DIP switch programming.)
SLCE-127's Back Panel Showing P-Link Terminal & Dip Switch Locations
Figure 55.
DETAIL G
SCALE 1 : 2
DWG #602-17
DWG #608-28
- + B
A
S1
SLC OUT SLC RET
-
+
-
+
Dip Switch
P-Link
from Control
Panel