3-35
PFC-6800 • 5403602 • Rev B • 2/13
The LeD-16 is controlled over the 4-wire P-Link connection. The higher current required for the LeD outputs can be provided
by the panel, or from an auxiliary power source as shown below. The auxiliary power can be any 24vDC source, and is fully
supervised.
Examples of Wiring LED-16 Module to Control Panel or Auxiliary Power Supply
Figure 35.
Setting Addresses
The LeD-16's address is set by
dip switch S1
, which is located on the back of the annunciator. The address must be set in the
range of one to thirty-one (1–31) to be recognized by the panel.
(Refer to the "P-Link Addresses" table shown earlier in this
section for DIP switch programming.)
LED-16 Back Panel Showing Dip Switch Location
Figure 36.
LED Drivers Installation (DRV-50)
The panel supports up to thirty-one (31) DRv-50s. each DRv-50 provides programmable LeD outputs and 4 programmable dry-
contact inputs, which can be individually mapped to any zone. The DRv-50 is controlled over the 4-wire P-Link connection, and
is installed onto a mounting bracket as shown below. This can then be mounted into any of the compatible fire enclosures, or in
either of the Ae-8 or Ae-14 accessory cabinets.
DRV-50 Module & Board
Figure 37.
LED PWR P -Link
-
+ -
+ A B
P-Link from
control panel
Example:
Powered by
control panel
LED PWR P -Link
-
+ -
+ A B
P-Link from
control panel
Example:
Powered by
aux supply
Power from
auxiliary
supply
DWG #608-6
DWG #608-7
DWG #608-23
P-Link
Connections
S1
Dip
Switches