HOUSING:
Type:
General purpose, indoor, steel enclosure with hinged removable cover and key lock.
Size:
18 1/2" X 14 1/4" X 4 3/4"
Finish:
Baked enamel, off-white with grey trim and red logo. Available in other colors and private labeling as
required by users (consult factory).
Knockouts:
8 combination 1/2" - 3/4" knockouts. 2 on each side, top and back.
Option:
Bezel for semi-flush mounting in a 4" wall.
VISUAL INDICATORS (With door closed):
AC ON:
Green LED comes on when AC voltage reaches 102 Volts, goes off when AC voltage drops below 96
Volts.
Alarm:
Red LED comes on when a zone is in alarm condition.
Discharged:
Red LED comes on when releasing circuit is activated.
Supervisory:
Yellow LED comes on for supervisory condition.
System Trouble:
Yellow LED comes on for any trouble condition. Possible conditions are Ground Fault, Initiation
Device Circuit Trouble, Supervisory Zone Activation, Supervisory Circuit Trouble, Indicating Appli-
ance Circuit Trouble, Abort, Abort Circuit Trouble, Battery Trouble, Zone Disable switch operated,
Auto Reset switch operated, AC Voltage Trouble, Releasing Circuit disabled.
LCD:
A two line, 32 character alpha-numeric liquid crystal display displays the condition, status and circuit
for all Alarm, Trouble and Supervisory conditions as illustrated. The time to discharge is shown when
the pre-discharge timer has been activated.