Potter PFC 2000RC Installation, Operation And Instruction Manual Download Page 17

17

PFC 2000RC • 5403521-REV N• 3/03

viewed at eye level.  The viewing angle can be adjusted slightly by the adjustment located just below the display.
MOUNTING  THE  BEZEL:

1) This unit may be surface mounted or semi-flush mounted by using the optional trim bezel.  For semi-flush installations mount

the housing so that the front edge protrudes 1" from the finished wall surface.

2) The main panel should be removed before attempting to mount the cabinet.  For instructions on removal of the Main Board

Module, refer to “Procedure for the Removal of the Main Board Module”.

3) Install all required conduits, external wiring and devices making all connections that are external to the panel.
4) If this is a semi-flush mount installation, after the wall surface is finished, slide the trim bezel in place and fasten with four

#6-32 screws as shown below.

INSTALLATION OF BEZEL FOR SEMI-FLUSH INSTALLATIONS

WIRING HOOKUP:

1) With the AC power turned off at the circuit breaker panel, connect the 120VAC HOT, NEUTRAL and GROUND wire to the

terminal block as shown on the power supply connection drawing.  Verify that the transformer cable is securely connected.

2) Connect all the other wiring to the terminals as shown in the main board connection drawings.  Plug the main board into the

card edge connection portion of the terminal strip.  Plug the power cable into the main board.  Turn the AC power on.
Observing proper polarity, connect the standby batteries with the cable provided.

3) The operation of the complete system should be verified as outlined in the test procedure section.

TEST PROCEDURES

CAUTION:

The system should be inspected and tested in compliance with NFPA-72 National Fire Alarm Code or the authority
having jurisdiction.

1) Notify the fire department or other receiving station of alarm, supervisory, and/or trouble signals that will be transmitted.
2) Notify the proper building personnel so that audible and/or visual, signals can be disregarded during testing.
3) Remove the two wires from the releasing circuit, reverse and reconnect them.  The panel should go to a trouble condition

and remain there (if the panel restores to a normal condition when the leads are reversed  it indicates that the diode in the
end of the line assembly is open and the solenoid valve can not operate until the entire EOL assembly, part #3005012, is
replaced).  Disconnect and restore the leads to their correct position.  The panel should restore to a normal condition.

4) Operate the Releasing Circuit Switch to the disable position. This will cause a trouble condition.
5) Momentarily operate the Test/Reset switch to the Test position. This will cause all audible and visual indicators to activate.

Releasing the Test switch will restore the panel to the condition it was in prior to operation of this switch.

6) Operate each zone switch to the disable position.  This should result in a trouble condition and operate all indicators as

described in the sections on “Trouble Conditions” and “Initiating Device Circuits Response”.  Restoring the switch to the
enable position should restore all indicators to normal.

7) Momentarily open each of the following circuits:

A) Each initiating device zone.  There is a brief delay when these circuits are in the Style D (Class A) mode.
B) Supervisory circuit.

firealarmresources.com

Summary of Contents for PFC 2000RC

Page 1: ...CT TO REVISION MANUAL 5403521 REVN 3 03 2081 Craig Road P O Box 28480 St Louis MO 63146 4161 800 325 3936 314 878 4321 FAX 314 878 7264 www pottersignal com INSTALLATION OPERATION AND INSTRUCTION MANU...

Page 2: ...ion or repair by unauthorized per sons or if for any other reason POTTER determines that said product is not operating prop erly as a result of causes other than defective manufacture labeling or pack...

Page 3: ...PLIANCE CIRCUITS 8 RELEASING CIRCUIT 9 ABORT CIRCUIT 9 PRE DISCHARGE TIMER 9 DISCHARGE TIMER 9 POWER REQUIREMENTS 10 AUXILIARY POWER OUTPUT 10 AUDIBLE INDICATOR 10 ELECTRONIC OUTPUTS 10 AUXILIARY CONT...

Page 4: ...ION INSTRUCTIONS 16 PROCEDURE FOR THE REMOVAL OF THE MAIN BOARD MODULE 16 LOCATION 16 MOUNTING THE BEZEL 17 INSTALLATION OF BEZEL FOR SEMI FLUSH INSTALLATIONS DRAWING 17 WIRING HOOKUP 17 TEST PROCEDUR...

Page 5: ...all alarm trouble and supervisory conditions in an English format 10 One man test feature 11 Compatible with 2 and 4 wire detectors 12 Power limited circuits 13 Single alarm trouble silence switch 14...

Page 6: ...m condition Discharged Red LED comes on when releasing circuit is activated Supervisory Yellow LED comes on for supervisory condition System Trouble Yellow LED comes on for any trouble condition Possi...

Page 7: ...circuits RESET SWITCH Momentary switch resets all alarm circuits if the condition has been corrected Removes power from the alarm initiating device circuit and also from the auxiliary power circuit if...

Page 8: ...equired for alarm is 5 mA Normal standby loop current is 3 mA End of line resistor is 5 1k ohms Minimum time to reset is 3 seconds SUPERVISORY INITIATING DEVICE CIRCUIT One Class B circuit Circuit is...

Page 9: ...the abort switch after a second alarm will not interrupt operation of the pre discharge timer PRE DISCHARGE TIMER Switch selectable from 0 to 60 seconds in 10 second increments with 4 switch selectab...

Page 10: ...IC OUTPUTS 24VDC 25mA with current limiting to 45mA for each of the following Alarm per zone 3 System Trouble Releasing Circuit activated System Alarm Supervisory Output for optional 4 pole relay see...

Page 11: ...lay 2 Operation of the red alarm LED 3 Operation of the auxiliary alarm contacts 4 Positive 24 VDC will appear on the associated zone electronic output terminal 5 Operation of one or both of the indic...

Page 12: ...he problem must be located and corrected SUPERVISORY CONDITION An increase in current to approximately 4 5 mA or greater in the supervisory circuit will result in the following 1 The words SUPV and SU...

Page 13: ...er located on the power supply board will be illuminated AUXILIARY POWER FAILURE Failure of the auxiliary power supply will result in the following 1 The words TROUBLE and AUX POWER will be displayed...

Page 14: ...on of a indicating appliance circuit that is the result of a current in excess of 1 5 Amps when the panel is in the alarm condition requires manual operation of the Reset switch SELECTING PANEL OPERAT...

Page 15: ...ISCHARGE TIMER ACTIVATION MODE There are 4 modes of starting the pre discharge timer from zones 1 and or 2 Select the desired mode by setting switches 9 and 10 as shown in the following Mode Operation...

Page 16: ...arm Code Central Station Proprietary and Local all local codes and the authority having jurisdiction Review the circuit parameters listed in the Specifications section of this manual before installing...

Page 17: ...st procedure section TEST PROCEDURES CAUTION The system should be inspected and tested in compliance with NFPA 72 National Fire Alarm Code or the authority having jurisdiction 1 Notify the fire depart...

Page 18: ...e test has been concluded OPERATINGINSTRUCTIONS Fill in the name address and telephone number of the servicing agency on the instruction sheet provided and post in a prominent place There are two Oper...

Page 19: ...tor Required AH x 001 x____ x 001 __ 85 TABLE 1 CURRENT REQUIREMENTS Module Device Standby mA Alarm mA PFC2000RC 85 240 Includes one zone short circuit current TABLE 2 SECONDARY POWER SUPPLY REQUIREME...

Page 20: ...AND OR CLASS 2 SOURCE ONLY 8 AUXILIARY POWER 24V MAX FOR LIMITATIONS SEE SECTION BATTERY SIZE REQUIREMENTS COMBINED LOAD ON THESE TERMINALS NOT TO EXCEED 500 MA MAX SEE SECTION ON COMPATIBILITY DATA...

Page 21: ...evice intended specifically for this purpose or by the use of one or more listed alarm pressure switches installed to monitor the pressure present in the suppression system the normally open contacts...

Page 22: ...y Activation Mode Selected 6 Dia Base 4 Dia Base Impedance Contact 1 or 2 single or cross zone HSB 221N YBA M221 390 ohms no HSC 221R 390 ohms yes 3 or 4 sequential or cross sequential HSB 221 YBA M21...

Page 23: ...23 PFC 2000RC 5403521 REV N 3 03 CONNECTION DRAWING POWER SUPPLY MODULE TYPICAL 4 WIRE DETECTOR CONNECTION DRAWING CLASS B CKT SHOWN firealarmresources com...

Page 24: ...24 PFC 2000RC 5403521 REV N 3 03 CONNECTION DRAWING FOR CENTRAL STATION PROPRIETARY OPERATION PFC EFT C INTERCONNECTION DRAWING PFC ATTE B INTERCONNECTION DRAWING firealarmresources com...

Page 25: ...25 PFC 2000RC 5403521 REV N 3 03 PFC 2000RC INNER PANEL DRAWING firealarmresources com...

Page 26: ...HB 71 NS6 221 NS4 221 SLR 24H HD 3 HSB 221N HB 54 HSB 221 HB 54 HSC 221R HB 71 NS6 221 NS4 221 SIJ 24 HD 3 HSB 221N HB 54 HSB 221 HB 54 HSC 221R HB 71 NS6 221 NS4 221 FENWAL MAX NO OF DETECTORS PER ZO...

Page 27: ...M 2 C 1 1 1 C O N V L N U 4 N B 8 1 2 3 7 C D V 4 2 r e l k n i r p S l a r t n e C A l e d o M 6 c n I o C r e l k n i r p S c i t a m o t u A e l b a i l e R A l e d o M X B d n a B s l e d o M 2 1...

Page 28: ...way from power input wiring battery leads and any other non power limited conductors NOTE All field installed wiring connected to this panel must maintain a spacing of 1 4 inch between all power limit...

Reviews: