PFC 2000RC • 5403521-REV N• 3/03
Switch selectable periods of 2 minutes or continuous.
POWER REQUIREMENTS
Input: 117VAC single phase, 60 Hertz, 100V Amps maximum
Standby: 24VDC, 85mA
Standby Batteries:
Gel cell sealed lead-acid batteries
Must be sized to provide the required standby period. 24 or 90 hours depending on the service required.
Alarm: 24 Volts - 240mA for first 2 mins. max., then 200mA.
AUXILIARY POWER OUTPUT
Regulated 24VDC, 500mA max.
Three terminal connections: one common negative, one positive that is interrupted on reset (for use with 4-wire detectors), and
one positive that is constant.
AUDIBLE INDICATOR
Built in buzzer operates on trouble conditions.
ELECTRONIC OUTPUTS
24VDC, 25mA with current limiting to 45mA for each of the following:
Alarm per zone (3)
System Trouble
Releasing Circuit activated
System Alarm
Supervisory
Output for optional 4 pole relay (see below)
AUXILIARY CONTACT OUTPUTS
System Alarm:
1 set SPDT (Form C)
System Trouble:
1 set SPDT (Form C)
Contacts rated 30 Volts, 2 Amps Resistive
Option:
System Alarm output - 4PDT (4 pole double-throw)
Contacts rated 30VDC/120VAC, 5 Amps Resistive
MAIN CIRCUIT BOARD MODULE
The Main Circuit Board Module is removable without disconnecting the field wiring.
TERMINATION
AC power input terminals and grounding terminal are capable of handling #12 AWG conductors. All other terminals are
capable of handling #14 AWG conductors.
OPERATING TEMPERATURE RANGE
32 to 120 degrees Fahrenheit
0 to 49 degrees Celsius
}
Use power limited and/or Class 2 source only