PFC 2000RC • 5403521-REV N• 3/03
Use a battery with a higher AH rating than Required AH
INACTIVE CIRCUITS
All inactive alarm and supervisory initiating device circuits and indicating appliance circuits must have the end-of-line resistor
installed on the panel terminals. On circuits that have four terminals, this resistor must be on the outside two terminals.
Total mA
Convert to A
Total A
5 min/12 or 10 min/6
Total Alarm AH
+ Total Standby AH
Total AH
Efficiency Factor
Required AH
x .001
x____
x .001
÷__
÷ .85
TABLE 1
CURRENT REQUIREMENTS
Module/Device
Standby mA
Alarm mA
PFC 2000RC
85
240*
*Includes one zone short circuit current.
TABLE 2
SECONDARY POWER SUPPLY REQUIREMENTS
NFPA Standard
Standby Time
Alarm Time
NFPA-72 National Fire Alarm Code
• Central Station Systems
24 hrs.
5 mins.
• Local Systems
24 hrs.
5 mins.
• Proprietary Systems
24 hrs.
5 mins.
FMRC 1011 & 1012, Deluge & Pre-action Systems
90 hrs.
10 mins.
CALCULATION TABLE
1
2
3
4
5
6
Module/Device
Quantity
Standby mA Per Unit
Total Standby Current
Alarm mA Per Unit
Total Alarm Current
Total mA
Convert to A
Total A
Multiply by hours from Table 2
Total Standby AH