15
PFC 2000RC • 5403521-REV N• 3/03
Style D (Class A)
Manual Ckt.
6
ON
SELECTING INDICATING APPLIANCE CIRCUIT MODE:
There are 3 modes of operation for the indicating appliance circuit. Select the desired mode by setting switches 7 and 8 as shown
in the following:
Mode
Operation
Switch No.
Position
1
Steady on first alarm, pulsating on second alarm or upon
7
ON
activation of manual circuit.
8
OFF
2
Pulsing on first alarm, steady on second alarm or upon activation of
7
OFF
manual circuit.
8
ON
3
No. 1 circuit activated on first alarm, No. 2 circuit activated on
7
ON
second alarm or upon activation of manual circuit.
8
ON
Note: Pulse time period is approximately 1/2 second.
SELECTING THE PRE-DISCHARGE TIMER ACTIVATION MODE:
There are 4 modes of starting the pre-discharge timer from zones 1 and/or 2. Select the desired mode by setting switches 9 and
10 as shown in the following:
Mode
Operation
Switch No.
Position
1
Single zone activation
9
ON
10
OFF
2
Cross zone activation
9
OFF
10
ON
3
Sequential activation
9
ON
10
ON
4
Sequential or cross zone (any 2 detectors)
9
OFF
10
OFF
NOTE: Mode 3 or 4 requires the use of Hochiki detectors and HSB-21 or YBA-M21 bases.
ACTIVATION FROM MANUAL CIRCUIT:
In addition to the above activation modes, there are two modes of activation from the manual device circuit. Select the desired
mode by setting switch 11 as shown in the following:
Mode
Operation
Switch No.
Position
1
Immediate discharge upon activation of the manual circuit.
11
OFF
2
30 second delay of discharge after activation of the manual circuit.
11
ON