Potter PFC 2000RC Installation, Operation And Instruction Manual Download Page 18

18

PFC 2000RC • 5403521-REV N• 3/03

7) Momentarily open each of the following circuits:

A) Each initiating device zone. There is a brief delay when these circuits are in the Style D (Class A) mode.
B)  Supervisory circuit.
C) Indicating Appliance circuits.
D) Abort Circuit.
Verify that this results in a trouble condition and all indicators operated as described in the appropriate preceding section for
the particular circuit that is faulted.

8) Turn off AC power at the circuit breaker panel. The green "AC ON" LED will be extinguished. Verify that all the trouble

indicators described in the section on "Loss or Reduction of AC Power" occur. Operated the Reset/Test switch to the Test
position. All audible and visual indicators should operate. Restore the switch to normal. Restore the AC power.

9) Operate the Auto Reset switch to the on position.
10) Operated each alarm imitating device on all zones. All audible and visual devices should operated. These devices will cease to

operate after  period of approximately 3 seconds. Power will automatically be removed from the initiating device circuit for
approximately 15 seconds. No alarm can be initiated during this period. If the imitating device has not been restore the panel
will go back into the alarm condition.

11) Operate each initiating device on the supervisory circuit. Verify that all the indications described in the section on

"Supervisory Conditions" occur.

12) Restore the Releasing Circuit Switch.
13) Return the Auto Reset switch to the off position. All the LED's on the panel except the green "AC ON" LED should be off. All

audible and visual indicators connected to the indicating appliance circuit should be off.

14) Notify all building personnel that the test has been concluded.
15) Notify the fire department or other receiving station that the test has been concluded.

OPERATING  INSTRUCTIONS

Fill in the name, address and telephone number of the servicing agency on the instruction sheet provided and post in a
prominent place. There are two Operating Instruction sheets provided, one if abort mode 1 is used and the other if abort mode
2 is used.

BATTERY  SIZE  REQUIREMENTS

These panels require a 24 Volt gel-cell battery for proper operation. 24 hours of standby power is required for NFPA 722-
Central Station Systems, Local Systems and Proprietary Systems.

The chart below will assist you in selecting the proper size battery:

Battery Size

    Hours of Standby

          Maximum Auxiliary Current Load

   4.0 AH

24

.100

    8.0 AH

24

.175

    8.0 AH

90

0

  12.0 AH

24

.250

  12.0 AH

90

.075

Note: Batteries rated above 10AH require a separate battery cabinet.

Alternate method of calculating battery size using the "Calculation Table" on page 19.

1)List in column #1 all devices used in the system, include all modules, bells, horns, door holders and smoke detectors (see Table

#1 or manufacturers specifications).

2) List in column #2 the quantity of each device.
3) List in column #3 the standby current of each device (exclude all indicating appliance devices).
4) List in column #5 the alarm current of each device.
5) For each line, multiply the figure in column #2 by the figure in column #3 and enter the product in column #4. Then multiply the

figure in column #2 by the figure in column #5 and enter the product in column #6.

6) Add the figures in column #3 and #6, then enter the sums in the appropriate Total mA box.
7) Convert these figures from milliampere to amperes by multiplying by .001, enter the product in the appropriate Total A box.
8) Multiply the standby total amperes by required time in hours from Table 2.
9) Divide the alarm total amperes by 12 for 5 min. or by 6 for 10 min. (see Table 2).
10) Add the standby AH and the alarm AH and divide this sum by .85 (Efficiency Factor). Select a battery that has an AH rating

above this figure but not less than 6.5 AH.

firealarmresources.com

Summary of Contents for PFC 2000RC

Page 1: ...CT TO REVISION MANUAL 5403521 REVN 3 03 2081 Craig Road P O Box 28480 St Louis MO 63146 4161 800 325 3936 314 878 4321 FAX 314 878 7264 www pottersignal com INSTALLATION OPERATION AND INSTRUCTION MANU...

Page 2: ...ion or repair by unauthorized per sons or if for any other reason POTTER determines that said product is not operating prop erly as a result of causes other than defective manufacture labeling or pack...

Page 3: ...PLIANCE CIRCUITS 8 RELEASING CIRCUIT 9 ABORT CIRCUIT 9 PRE DISCHARGE TIMER 9 DISCHARGE TIMER 9 POWER REQUIREMENTS 10 AUXILIARY POWER OUTPUT 10 AUDIBLE INDICATOR 10 ELECTRONIC OUTPUTS 10 AUXILIARY CONT...

Page 4: ...ION INSTRUCTIONS 16 PROCEDURE FOR THE REMOVAL OF THE MAIN BOARD MODULE 16 LOCATION 16 MOUNTING THE BEZEL 17 INSTALLATION OF BEZEL FOR SEMI FLUSH INSTALLATIONS DRAWING 17 WIRING HOOKUP 17 TEST PROCEDUR...

Page 5: ...all alarm trouble and supervisory conditions in an English format 10 One man test feature 11 Compatible with 2 and 4 wire detectors 12 Power limited circuits 13 Single alarm trouble silence switch 14...

Page 6: ...m condition Discharged Red LED comes on when releasing circuit is activated Supervisory Yellow LED comes on for supervisory condition System Trouble Yellow LED comes on for any trouble condition Possi...

Page 7: ...circuits RESET SWITCH Momentary switch resets all alarm circuits if the condition has been corrected Removes power from the alarm initiating device circuit and also from the auxiliary power circuit if...

Page 8: ...equired for alarm is 5 mA Normal standby loop current is 3 mA End of line resistor is 5 1k ohms Minimum time to reset is 3 seconds SUPERVISORY INITIATING DEVICE CIRCUIT One Class B circuit Circuit is...

Page 9: ...the abort switch after a second alarm will not interrupt operation of the pre discharge timer PRE DISCHARGE TIMER Switch selectable from 0 to 60 seconds in 10 second increments with 4 switch selectab...

Page 10: ...IC OUTPUTS 24VDC 25mA with current limiting to 45mA for each of the following Alarm per zone 3 System Trouble Releasing Circuit activated System Alarm Supervisory Output for optional 4 pole relay see...

Page 11: ...lay 2 Operation of the red alarm LED 3 Operation of the auxiliary alarm contacts 4 Positive 24 VDC will appear on the associated zone electronic output terminal 5 Operation of one or both of the indic...

Page 12: ...he problem must be located and corrected SUPERVISORY CONDITION An increase in current to approximately 4 5 mA or greater in the supervisory circuit will result in the following 1 The words SUPV and SU...

Page 13: ...er located on the power supply board will be illuminated AUXILIARY POWER FAILURE Failure of the auxiliary power supply will result in the following 1 The words TROUBLE and AUX POWER will be displayed...

Page 14: ...on of a indicating appliance circuit that is the result of a current in excess of 1 5 Amps when the panel is in the alarm condition requires manual operation of the Reset switch SELECTING PANEL OPERAT...

Page 15: ...ISCHARGE TIMER ACTIVATION MODE There are 4 modes of starting the pre discharge timer from zones 1 and or 2 Select the desired mode by setting switches 9 and 10 as shown in the following Mode Operation...

Page 16: ...arm Code Central Station Proprietary and Local all local codes and the authority having jurisdiction Review the circuit parameters listed in the Specifications section of this manual before installing...

Page 17: ...st procedure section TEST PROCEDURES CAUTION The system should be inspected and tested in compliance with NFPA 72 National Fire Alarm Code or the authority having jurisdiction 1 Notify the fire depart...

Page 18: ...e test has been concluded OPERATINGINSTRUCTIONS Fill in the name address and telephone number of the servicing agency on the instruction sheet provided and post in a prominent place There are two Oper...

Page 19: ...tor Required AH x 001 x____ x 001 __ 85 TABLE 1 CURRENT REQUIREMENTS Module Device Standby mA Alarm mA PFC2000RC 85 240 Includes one zone short circuit current TABLE 2 SECONDARY POWER SUPPLY REQUIREME...

Page 20: ...AND OR CLASS 2 SOURCE ONLY 8 AUXILIARY POWER 24V MAX FOR LIMITATIONS SEE SECTION BATTERY SIZE REQUIREMENTS COMBINED LOAD ON THESE TERMINALS NOT TO EXCEED 500 MA MAX SEE SECTION ON COMPATIBILITY DATA...

Page 21: ...evice intended specifically for this purpose or by the use of one or more listed alarm pressure switches installed to monitor the pressure present in the suppression system the normally open contacts...

Page 22: ...y Activation Mode Selected 6 Dia Base 4 Dia Base Impedance Contact 1 or 2 single or cross zone HSB 221N YBA M221 390 ohms no HSC 221R 390 ohms yes 3 or 4 sequential or cross sequential HSB 221 YBA M21...

Page 23: ...23 PFC 2000RC 5403521 REV N 3 03 CONNECTION DRAWING POWER SUPPLY MODULE TYPICAL 4 WIRE DETECTOR CONNECTION DRAWING CLASS B CKT SHOWN firealarmresources com...

Page 24: ...24 PFC 2000RC 5403521 REV N 3 03 CONNECTION DRAWING FOR CENTRAL STATION PROPRIETARY OPERATION PFC EFT C INTERCONNECTION DRAWING PFC ATTE B INTERCONNECTION DRAWING firealarmresources com...

Page 25: ...25 PFC 2000RC 5403521 REV N 3 03 PFC 2000RC INNER PANEL DRAWING firealarmresources com...

Page 26: ...HB 71 NS6 221 NS4 221 SLR 24H HD 3 HSB 221N HB 54 HSB 221 HB 54 HSC 221R HB 71 NS6 221 NS4 221 SIJ 24 HD 3 HSB 221N HB 54 HSB 221 HB 54 HSC 221R HB 71 NS6 221 NS4 221 FENWAL MAX NO OF DETECTORS PER ZO...

Page 27: ...M 2 C 1 1 1 C O N V L N U 4 N B 8 1 2 3 7 C D V 4 2 r e l k n i r p S l a r t n e C A l e d o M 6 c n I o C r e l k n i r p S c i t a m o t u A e l b a i l e R A l e d o M X B d n a B s l e d o M 2 1...

Page 28: ...way from power input wiring battery leads and any other non power limited conductors NOTE All field installed wiring connected to this panel must maintain a spacing of 1 4 inch between all power limit...

Reviews: