20
PFC 2000RC • 5403521-REV N• 3/03
PFC 2000RC MAIN BOARD CONNECTION DRA
WING (IDENTIFIER "A")
USE WIRE ROUTING DRAWING, PAGE 28
NOTES:
1.)
USE ONL
Y SMOKE DETECT
ORS THA
T ARE LISTED
IN COMP
A
TIBILITY LIST
, ON INSIDE OF DOOR.
2.)
ANY ZONE CAN BE OPERA
TED IN A CLASS A
MODE. PLEASE REFER T
O
INSTRUCTION
MANUAL. THE END- OF-LINE RESIST
OR IS IN THE
P
ANEL WHEN CLASS A MODE IS USED.
3.)
WHEN USED IN A SEQUENTIAL OR CROSS
SEQUENTIAL MODE USE ONL
Y
HOCHIKI
DETECT
ORS WITH YBA-M21 OR HS-21D BASES.
4.)
LEA
VE END-OF-LINE RESIST
ORS ON INACTIVE
CIRCUITS.
5.)
ALL CIRCUITS POWERED BY THIS CONTROL ARE
POWER LIMITED.
6.)
COMBINED LOAD OF ALL EXTERNAL DEVICES
INCLUDING INDICA
TING DEVICES NOT T
O
EXCEED 3 AMPS.
7.)
AUX. CONT
ACTS RA
TED 2A 30 VDC
RESISTIVE.
ALL AUXILIAR
Y
CONT
ACTS ARE SHOWN IN
THE NORMAL CONDITION. NOT T
O
BE USED
FOR MOT
OR LOADS OR PILOT DUTY
APPLICA
T
IO
N
.
W
ARNING:
EXCEEDING RECOMMENDED
RA
TINGS MA
Y VOID W
ARRANTY! USE
POWER LIMITED CIRCUIT AND/OR CLASS 2
SOURCE ONL
Y
.
8.)
AUXILIAR
Y POWER 24V MAX.
FOR LIMIT
A
TIONS, SEE SECTION "BA
TTER
Y
SIZE REQUIREMENTS"
COMBINED LOAD ON THESE TERMINALS NOT T
O
EXCEED 500 MA. MAX.
SEE SECTION ON "COMP
A
TIBILITY DA
T
A".
9.)
FOR MAX. CURRENT
, RESIST
ANCE, AND MIN. BA
TTER
Y
VOL
T
AGE, SEE SECTION ON "RELEASING CIRCUIT".
FOR LIST OF COMP
A
TIBLE SOLENOIDS AND V
A
L
VES,
SEE SECTION ON "EXTINGUISHING AGENT CONTROL
V
A
L
VE COMP
A
TIBILITY DA
T
A".
10.) POLARITY SHOWN ON BELL AND RELEASING CIRCUITS
IS FOR NORMAL ST
ANDBY CONDITION. REVERSES T
O
ACTIV
A
TE DEVICES. CONNECT THE NEGA
TIVE LEAD
OF THE INDICA
TING APPLIANCE T
O
THE POSITIVE
TERMINAL OF THE P
ANEL. CONNECT THE POSITIVE
LEAD OF THE INDICA
TING APPLIANCE
T
O
THE NEGA
TIVE TERMINAL OF THE
P
ANEL.
1
1.) END OF LINE DIODE ASSEMBL
Y
(
P
AR
T
#3005012) MUST BE LOCA
TED A
T
SOLENOID V
A
L
VE LOCA
TION.
12.) COMBINED LOAD OF INDICA
TING AND
RELEASING CIRCUITS NOT T
O
EXCEED
2.5 AMPS.
13.) IF OPTIONAL AUXILIAR
Y RELA
Y MODULE
ARM-2 IS USED ON THIS CIRCUIT
, THE
ADDITIONAL POWER REQUIRED BY THE
RELA
Y MUST BE SUBTRACTED FROM
THE
T
O
T
AL CIRCUIT CURRENT NOTED.
SEE BULLETIN #5400977.
SEE APPLICATION NOTE 1 ON PAGE 21.
firealarmresources.com