background image

 

CROSSED LINES WARNING 

N E W   O R   M O D I F I E D   I N S T A L L A T I O N S  

ALWAYS ASSURE THAT LINES ARE NOT CROSSED!

 

 

 

WARNING:

  New or modified installations - 

properly connected gas pipelines are absolutely essential 

to patient safety.

  The dealer or contractor should provide written documentation that all gas pipelines are 

connected properly and that the system has been pressure tested prior to use.  While this is a good 
business practice, it is important that the user verify by their own test, independent of the dealer or 
contractor, that all gas pipelines are connected correctly prior to using the system.  

The ultimate 

responsibility of assuring that lines are not crossed rests with the user. 
 
Do not allow crossed lines to defeat the safety features of the dental flowmeter and / or central gas 
supply manifold systems.  Crossed lines will create a dangerous and hazardous condition where 
100% Nitrous Oxide will be delivered through the Oxygen dental flowmeter tube and subsequently 
to the patient.  In addition, the resuscitator quick connect would deliver 100% Nitrous Oxide to an 
Oxygen demand valve.   
 
Maintain patient observation during procedures.  Prevent over sedation.  If a patient becomes over 
sedated when being delivered 100% Oxygen, it is a definite indication of crossed lines.  If crossed 
lines are suspected, remove the nasal mask immediately and encourage mouth breathing.  Deliver 
pure Oxygen from an Oxygen demand valve only if the Oxygen source is independent from the 
suspected crossed lines area.   
 

To check for crossed lines of an installed Porter Vanguard (or Sentinel) Manifold System: 

 

1.  At the manifold system (in the tank room), start the check from an operating system with 50 PSI 

showing on both gauges and the indicator lights turned on – electrical operation and alarms needed for 
the Vanguard test.  Then, turn off both Oxygen tanks and leave both Nitrous Oxide tanks on.  (For the 
Sentinel, only one tank of each gas is on at a time.  Turn off the one open Oxygen tank, leave on the 
one Nitrous Oxide tank, turn off the indicator lights – eliminates alarms during the Sentinel test.) 

 

2.  In the operatory, where the flowmeter is installed, flow 5 to 6 liters per minute of O

2

 only. Verify that the 

N

2

O flowmeter valve is in the off position and that there is no indicated flow of N

2

O - by observing the 

ball float resting at the bottom of the glass N

2

O flow tube.    

 

This action will bleed the Oxygen copper tubing lines (1/2” OD) from the manifold, through the office 
walls, to the flowmeter.  Note: this action does not cause a quick bleed down, as there is a fair sized 
volume in the lines.  O

flow would be observed by the position of the ball float in the O

2

 flow tube for 

several minutes. 

 

3.  Rather than waiting for the O

2

 flow to decrease, go back to the manifold tank room and observe the O

2

 

pressure gauge on the manifold (normally showing approximately 50 PSIG pressure).  The line 
pressure should start to decrease, indicating bleeding of the O

that is no longer being replenished by 

the tanks.  On Vanguard systems, the alarm will beep at 40 PSIG, a switch will occur from one tank to 
the second tank at a timed interval (increasing the gauge back to 50 PSIG).  The gauge then should 
eventually go down to zero.  

 

If the O

2

 pressure does not go down as described above, and remains at about 50 PSIG, it indicates a 

crossed lines condition. 

 

4. If 

O

pressure  does not go down, proceed to the next crossed line determination check.  Turn N

2

tanks off in the manifold tank room and watch the N

2

O

 

gauge. Given a crossed line condition, the N

2

O

 

gauge will now go down (the Vanguard system will show a switching similar to step 2 above) — this 
shows the O

2

 valve of the flowmeter is bleeding the crossed N

2

O lines.  The N

2

O gauge will go down to 

zero. 

 

 

7

Summary of Contents for 4065D

Page 1: ...DIGITAL MXR D Cabinet Mount Flowmeter Component Diagram and Installation Instructions MODEL 4065D FM 1062 Rev B 6 07...

Page 2: ...CSA C22 2 No 601 1 M90 Symbol Description Protective Earth Ground Class I Device Alternating Current Earth Ground Attention consult the accompanying documents Type B Equipment Distribution of Porter M...

Page 3: ...s 9 NFPA Codes 9 INTENDED USE Flowmeter for Analgesia Delivery System 9 INSTALL THE GAS LINES 10 SWITCHING THE UNIVERSAL CONNECTORS 10 CABINET WALL MOUNT INSTALLATION 11 FLOWMETER ACCESSORIES 13 CHECK...

Page 4: ...is to be wired per NEC and local electrical codes The branch circuit breaker is the main disconnect Porter recommends the following 15A UL circuit breaker two wire with ground TANK REGULATOR SPECIFICA...

Page 5: ...anual the safety protection provided by the equipment might be impaired The Porter Digital MXR D is designed to be used in normal environmental conditions 1 Indoor use 2 Altitude up to 8000 feet 2 438...

Page 6: ...904 or call 1 800 344 3555 WARNING New or modified installations properly connected gas pipelines are absolutely essential to patient safety The dealer or contractor should provide written documentati...

Page 7: ...nd alarms needed for the Vanguard test Then turn off both Oxygen tanks and leave both Nitrous Oxide tanks on For the Sentinel only one tank of each gas is on at a time Turn off the one open Oxygen tan...

Page 8: ...outlet station the Oxygen 1 2 inch pipe is incorrectly decreased down to the DISS 3 8 inch size reserved for Nitrous Oxide lines Oxygen is fed into the Nitrous Oxide lines At gas outlet station the c...

Page 9: ...Analgesia Delivery System This device is intended for patient adult and pediatric use by an attending physician or dentist properly trained in its use Porter Instrument recommends the user be thorough...

Page 10: ...ter The dental dealer is responsible for the final connections to the flowmeter the details of flowmeter installation checking for crossed lines leak testing of connections to the flowmeter and basic...

Page 11: ...ce a piece of tape over the rear power supply connector temporarily so dry wall dust does not enter the connector Wrenches required 7 8 for N2O connector 5 8 for O2 connector and 7 16 for mixed gas co...

Page 12: ...e O2 shut off valve and the N2O DISS hose blue to the N2O shut off valve 9 Run 20 feet mixed gas hose from flowmeter mixed gas outlet hose barb to hose barb of Remote Surface Mount or Through Wall Ada...

Page 13: ...ff position Confirm that the DISS Shut Off Valves are in the open position Pressurize the sedation gas supply lines with 50 PSI Observe any pressure decay after an overnight time period 5 PSI drop all...

Page 14: ...POWER SUPPLY SYSTEM ILLUSTRATION 14...

Page 15: ...GAS DISTRIBUTION SYSTEM ILLUSTRATION 15...

Page 16: ...w Knobs to full mechanical stops Installation Check for proper display STEP 1 N2O L M There is no Oxygen flowing There is no Nitrous flowing N2O and Total Flow valves are shut tightly Normal display c...

Reviews: