INSTALLATION
GUIDE
WIRING
CONNECTIONS
(wiring diagrams are located in the Appendix)
POSITION
FUNCTION
DESCRIPTION
1
Electric Lock Relay
Common.
2
Electric Lock Relay
N.O. Dry contact – Contact closes upon activation. May be used for fail-secure locks by
routing 1 leg of power through the relay. Relay is triggered by activation inputs 10, 11, or 16.
Relay remains energized until door is fully closed again.
3
Electric Lock Relay
N.C. Dry Contact - Contact opens upon activation. May be used for fail-safe locks by routing 1
leg of power through the relay. Relay is triggered by activation inputs 10, 11, or 16. Relay
remains energized until door is fully closed again.
4
Door Status - Closed
N.O. Contact is closed when door is closed. The contact opens as soon as the door opens.
5
Door Status – Common
Common contact for door status.
6
Door Status - Open
N.C. – Contact is closed when door is open. The contact opens as soon as the door starts to
close. This input can be used for motor connection at lockout relay when power is looped
through, thus switching power on when door is open.
7
GND
Common GND.
8
GND
Common GND.
9
+ 24 VDC
I A. Max Current.
10
Internal Activation
Requires N.O. Contact between input 10 & COM. Remains capable to activate when dip
switch 3 is ON AND On-Off switch is OFF.
11
External Activation
Requires N.O. Contact between input 11 & COM.
12
Emergency Closing
Requires N.C. contact between 12 & COM. Upon open contact, door closes and overrides all
other inputs. Remains jumpered if input is not used.
13
Secondary Activation
Requires N.C. contact between 13 & COM. Disabled in full closed position.
14
“Stall” Safety
Requires N.C. contact between 14 & COM. Upon open contact, (Dip 6 OFF) during opening,
door stops, then resumes at reduced speed when input is released.
15
KEY
KEY INPUT.
16
Alarm Input
N.O. contact, when closed causes door closing. All inputs inhibited during closed contact
(not available on all software versions).
17
Overhead Presence Sensor
Input
Requires N.O. contact between 14 & +24 VDC (input 9). When input is closed it causes an
open door to stay open and a closed door to stay closed. Works in conjunction with dip
switch #6.
18
GND
Common GND.
19
GND
Common GND.
20
Aux Relay
Auxiliary Relay NOTE: Relay is triggered by input 14.
21
Aux Relay
Auxiliary Relay N.O.
22
Aux Relay
Auxiliary Relay N.C.
23
Alarm Output - Common
Common.
24
Alarm Output
N.O. output is closed upon closed contact from fire alarm. LED 2 also illuminates.
25
+ 24 VDC
I A. Max Current.
26
GND
Common GND.
INPUTS 27 & 28 NOT USED
I/O BOARD
CONNECTIONS
TE
RM
IN
AL
S
TR
IP
J5
TE
RM
IN
AL
S
TR
IP
J6