background image

TECHNICAL DATA

FUNCTION

The  4000W  heating  unit  is  installed  in  the  foundation 

slab or intermediate floor, and contains a fan and four 

water/air-exchangers, with valves that are controlled by 1 

- 4 external electric room thermostats.  It is used together 

with heating unit box 4000A 100/100 (100 mm (4") spiral 

pipes) or with heating unit box 4000A 50/50 (50 mm (2") 

plastic pipes).

Operating voltage ........................1 P - 230V/24V 60Hz

Fan motor power consumption ............................225W

Breaker rating (GFI required) ................................. 15A

Water-air exchanger output

 with 8 - 100 mm duct ........approx. 5 kW @ 55°C/130°F

 

air flow .............. approx. 900 m

3

/h / 530 CFM   

 with 20 - 50 mm duct ........approx. 4 kW @ 55°C/130°F

      

air flow .............. approx. 750 m

3

/h / 440 CFM

Air temperature range.................... 30-55°C /85-130°F 

Connection, pipe......lavatory style, 1/2" straight thread

Design data for all 4 exchangers and valves:

Design flow ................................ 400 l/h / 1.75 USGPM

Design pressure drop ................. 21.5 kPa/7.2’/3.1 PSI

Maximum full flow pressure drop (noise limited):

......................................................35 kPa/11.2’/5.1 PSI

Maximum zero flow pressure drop (i.e. maximum pump

pressure, noise limited) ..................... 40 kPa/15’/7 PSI
This data is generic. Each Legalett installation is unique. 

Refer to customized specifications on your installation 

design drawing for actual design parameters.

15A circuit breaker

1 P - 230V 60Hz

thermostats 1-4

The 4000W is controlled  by one (single  zone) to four 

(quad zone) external electric room thermostats.  These 

external thermostats operate the control valves in the unit, 

opening the control valve when the room needs heat.  

A water temperature sensor built into the 4000W starts 

the fan motor when the inlet water temperature reaches 

30°C (85°F)  When the control valve is closed and the 

inlet water temperature decreases to approximately 27°C 

(80°F), the fan motor stops.  The fan operation is inde

-

pendent of the position of the zone valve, and responds 

only to water temperature.
When  controlled  by  a  programmable  thermostat,  the 

4000W can use two-tiered energy rates for night storage of 

less expensive energy in the LEGALETT heated floor.

www.legalett.com

January, 2006

Revised:May, 2008

Form № 0524

Page 1 of 2

HEATING UNIT - 4000W

Reviews: