INSTALLATION
GUIDE
APPENDIX
- FIRE RATED DOOR APPLICATION
§
Perform the installation according to the instructions outlined in this manual. Additionally, ensure the following
conditions have been met:
o
When attaching the door arm to the door, use steel binding posts
(Hex Bolts) to attach. Do NOT use sheet metal screws into the face
of the door. The door arm bracket must be through-bolted.
o
When attaching the header to the hollow metal door
frame, ensure there are 5 attaching screws spaced equally
apart. They should be #12 sheet metal type screws.
o
Fire rated power operated doors must close and latch during a fire alarm condition. Ensure proper
procedures have been followed to allow a main power disconnect during a fire alarm condition. Always
check to ensure compliance to local building codes.
•
Upon job completion, always perform a functional test to ensure that the door(s) close and latch
following a power loss.
o
Other hardware may be required to complete the installation. For example, for pairs of doors, if an
Astragal is installed, a mechanical door coordinator may be required to ensure a proper coordinated
closing during a power loss.
o
Only fire rated hardware shall be used on a fire rated door & frame assembly.
o
Ensure the Tucker SW10/19 that is being installed has the proper fire rated label applied to the header.
WWW.PORTALP.COM
|
52
Automatic Doors & Building Access Control
TUCKER SW10
(Full Power) & S
W19
(Low Energy)