15
8.15
Mixer settings
Settings of the mixer can be found in:
MENU -> MIXER 1 SETTINGS
The preset temperature of mixer cycle 1 can
be specified:
-
manually, by setting the parameter
preset mixer temperature
at the
required value, or
-
in relation to weather, by enabling
weather control and choosing the
appropriate heating curve.
In order to enable the weather control,
weather sensor must be connected. After
connecting the sensor, set the parameter
Mixer out. temp. dep.
to
on.
The mixer heating cycle can include a room
thermostat,
which
lowers
the
preset
temperature by the given value, both with
manual and weather control.
After
attaching
an
additional
module, the regulator can be
extended by 2 additional heating
cycles.
8.16
Weather control
Weather control can be enabled both for the
boiler cycle, and for the mixer cycle. After
selecting appropriate heating curve, the
preset temperature of boiler or mixer is
calculated automatically, depending on the
outdoor temperature. If the heating curve is
appropriate for the given building too, this
allows to maintain a constant temperature
inside,
regardless
of
the
temperature
outside. Therefore, it is crucial to select a
proper heating curve.
Guidelines for setting proper
heating curve:
- floor heating
0,2 -0,6
- radiator heating
1,0 - 1,6
- boiler
1,8 - 4
Drawing 15 heating curves:
Tips for selecting appropriate heating
curve:
- if the temperature inside rises while the
temperature outside drops, the selected
heating curve is too high,
- if the temperature inside drops while the
temperature outside drops as well, the
selected heating curve is too low.
Poorly insulated buildings require higher
heating curves. Whereas for well-insulated
buildings the heating curve will be lower.
The regulator can increase or decrease the
preset temperature calculated in the basis of
the heating curve if it goes beyond the
temperature range for the given cycle.
8.17
Description
of
setting
night-time
decreases
In the regulator menu, you can set time
periods for: boiler, heating cycles, and
domestic hot water tank.
The time periods allow to lower the preset
temperature in the given time period, e.g. at
night, or when users leave the heated rooms,
e.g. when they go to work. This allows to
decrease the temperature automatically,
which
increases
thermal
comfort
and
decreases fuel consumption.
In order to activate the time periods, set the
parameter
Night time temp. red.
to
on
in:
MENU -> NIGHT TIME TEMP. RED.
The night-time decreases can be specified
separately for weekdays, Saturday and
Sunday.