OPERATING AND INSTALLATION INSTRUCTIONS LG 250 A
PAGE 54
Changes reserved
U
S
ER
G
ENER
A
L
S
P
EC
IA
LIS
T
P
ER
S
O
NNEL
18. Fault description
Error descriptions are provided for the
corresponding light patterns in the follow-
ing table.
Errors can be located precisely using the
service software (available to specialist
personnel only).
Model
Error
Flashes once
Z05
Flashes twice
Z04
Flashes three times
Z06, Z07, Z08, Z09, Z10, Z11, Z12, Z13, Z14, Z15
Flashes 4 times
Z01, Z03, Z17, Z18, Z21
Flashes 5 times
Z02
Filter LED lights up
Z16
Model
Error
Z01
Inspect geothermal heat exchanger if supply air/extract air tempera-
ture is exceeded
Z02
Fault during data transmission
Z03
Danger of freezing - hot water re-heater battery
Z04
Exhaust air fan blocked
Z05
Supply air fan blocked
Z06
Short circuit temperature sensor T1
Z07
Short circuit temperature sensor T2
Z08
Short circuit temperature sensor T3
Z09
Short circuit temperature sensor T4
Z10
Short circuit temperature sensor T5
Z11
Outage temperature sensor T1
Z12
Outage temperature sensor T2
Z13
Outage temperature sensor T3
Z14
Outage temperature sensor T4
Z15
Outage temperature sensor T5
Z16
Replace extract air/outdoor air filter (filter LED lights up)
Z21
Re-heater battery frost protection active
19. Installation/Operation of service software and firmware updates
The control unit must be connected to a
laptop via the micro-USB cable in order to
perform troubleshooting.
Further information on installation/opera-
tion of service software and firmware up-
dates is available from certified partners
on request.
Service hotline:
+43 (0)463 32769-290
Email: