OPERATING AND INSTALLATION INSTRUCTIONS LG 250 A
PAGE 26
Changes reserved
U
S
ER
G
ENER
A
L
S
P
EC
IA
LIS
T
P
ER
S
O
NNEL
The characteristic curves shown are valid
for the unit version with Class F7 (EN 779)
outdoor air and G4 (EN 779) extract air
fi lters, as well as the version with no PTC
preheater battery.
The rated overall output comprises the
power consumption of the two supply
and exhaust air fans as well as the power
consumption of the control system.
CHARACTERISTIC CURVE - EXTERNAL
PRESSURE INCREASE – AIR VOLUME
FLOW
SOUND DATA
Level I
= 80 m³/h
Level II
= 160 m³/h
Level III
= 250 m³/h at external pressure
increase of 100 Pa
Note:
Tolerances ± 2 dB for acoustic data
Measuring
point
Housing
radiation
Outdoor air
connection
Supply air
connection
Exhaust air
connection
Extract air
connection
Level
I
II
III
I
II
III
I
II
III
I
II
III
I
II
III
63 Hz
Lw in dB
55
57
57
64
65
65
79
80
81
76
73
75
66
69
67
125 Hz
50
53
55
55
59
61
67
71
73
69
69
71
52
57
60
250 Hz
41
45
50
51
57
60
63
70
73
62
65
70
49
55
59
500 Hz
35
38
42
39
44
46
55
61
66
55
55
60
34
42
45
1000 Hz
32
36
40
30
33
37
55
62
66
54
56
59
24
31
36
2000 Hz
22
27
34
19
24
29
46
56
61
46
48
53
21
31
36
4000 Hz
15
17
25
12
17
22
39
49
55
39
42
48
17
28
33
8000 Hz
18
18
18
11
12
15
35
46
52
35
37
44
12
17
23
Total
LWA in dB(A)
39
42
46
45
49
52
60
67
70
59
61
65
43
48
51
The LG 250 A compact ventilation unit is
used for controlled, mechanical ventilation
and deaeration of homes, large residential
units and offi
ces and for similar purposes.
The scope of application normally extends
to living spaces between
80 m² and approx. 200 m², with an
adjustable air fl ow of up to
250 m³/h.
The LG 250 A compact ventilation
unit, comprising a compact, non-heat
bridging and thermally-insulated housing
made from galvanised steel sheeting,
externally powder-coated in RAL 9010,
a high-effi
ciency heat recovery system
with air/air-counterfl ow heat exchanger
made from recyclable plastic with a
temperature change rate of 84.7 %,
automatic 100 % bypass, with energy-
saving DC radial fans with constant fl ow
regulation, a fi lter ISO ePM2,5 65% in the
outdoor air and a fi lter ISO Coarse 90%
extract air, an internally wired electronic
control system and a “MINI” control
unit (optional). "TOUCH" for fl oor or wall
mounting in frost-free spaces.
VENTILATION UNIT