unit from bending down (See the figure below). Too much weight in the rear may cause permanent
damage to the enclosure.
Figure 8: Cable Support
Each outlet will pass the connected power through from the corresponding power input. Note that
the PowerGate2 is designed for 120VAC circuits only. Each outlet is limited to 15 Amps max via
breakers mounted on the front panel.
Latched Power to Outlets
The PowerGate2 design features latching power circuits. Each outlet remains latched ON as long
as power is applied to the corresponding input. This holds true even if main power to the unit is
removed. This allows you to pass power from a UPS through the PowerGate2 to your equipment,
without worrying about the PowerGate2 losing power.
PowerGate2 Setup via the IMS ConsoleView Software
The PowerGate2 will automatically be recognized by the IMS Host or Node. Within the IMS tree
structure an entry called
PowerGate2
will appear within the submenu of the Host and/or Node. To
expand the Host or Node submenus you must click the box with the plus sign next to the appropri-
ate Host or Node. The figure below shows the menu location of a PowerGate2 connected to a Host.
Figure 9: PowerGate2 in Hierarchy
To assign labels to the PowerGate2, right-click on
PowerGate2
. The following screen will appear:
Chapter 6: PowerGate2
103
Summary of Contents for Sensaphone IMS-4000
Page 1: ...IMS 4000 User s Manual Version 2 4 8 PHONETICS INC SENSAPHONE ...
Page 44: ......
Page 59: ......
Page 60: ......
Page 102: ......
Page 106: ...IMS 4000 Manual 106 ...
Page 135: ...Chapter 7 IMS 4000 Sensors 135 ...
Page 146: ...IMS 4000 Manual 146 ...
Page 148: ...IMS 4000 Manual 148 ...
Page 158: ...IMS 4000 Manual 158 ...
Page 159: ...159 ...