Configuration and startup
4063_en_B
PHOENIX CONTACT
4.10.2
LEDs
The GW PN/DP 1E/1DB9 provides four LEDs.
Table
4-2
Status LED descriptions
LED
Status
Description
ST
Off
Normal operation.
Solid green
Device initializing.
Flashing green (1
Hz)
Signal request due to DCP request.
PB
Flashing red (1
Hz)
PROFIBUS controller initialization.
Flashing red (2
Hz)
PROFIBUS telegram error, such as malformed tele-
gram frames.
Solid red
Configuration issue, such as a slave(s) configured
incorrectly or missing.
Solid green
PROFIBUS linked to network.
Flashing green (2
Hz)
No slaves configured for data exchange or PROF-
INET master in "Stop" mode.
Off
PROFIBUS master is offline.
BF
Flashing red (2
Hz)
No active connection to PROFINET controller.
Off
Normal operation.
SF
Flashing red (10
Hz)
PROFINET diagnostics present.
Off
Normal operation.