Connecting the RS-485 cable
The D-SUB
9 port connects to a PROFIBUS
DP network and functions as a master.
NOTE:
Observe the polarity of the RS-485 cable.
Install SUBCON-PLUS-PROFIB/90/PG/SC termination plugs (Order number 2313708) at
the furtherest ends of the PROFIBUS
DP network.
Table
3-1
RS-485 pinout
Pos.
Signal
Description
1
–
Not connected
2
–
Not connected
3
B
Data line (+)
4
CNTR P
RTS (TTL direction control for repeaters)
5
GND
Ground
6
+5 V
Supply voltage for terminator resistance
7
–
Not connected
8
A
Data line (-)
9
CNTR N
Neutral signal for active PROFIBUS cabling
3.2.2
Connecting the Ethernet cable
The GW PN/DP 1E/1DB9 has an Ethernet interface on the front in RJ45 format, to which
only twisted-pair cables with an impedance of 100
can be connected. The data
transmission rate is either 10 or 100 Mbps. The GW PN/DP 1E/1DB9 supports the auto
negotiation function for automatic selection of the transmission speed, as well as an
automatic crossover feature for the selection of line or crossover cabling.
Push the Ethernet cable with the crimped RJ45 connector into the GW PN/DP 1E/1DB9 until
it engages with a click.
3.3
Connecting the power supply
CAUTION:
Incorrect connection may result in damage to equipment and/or serious personal injury.
Only qualified personnel may connect the power, start up, and operate this device.
According to the safety instructions in this text, qualified personnel are persons who are
authorized to start up, to ground, and to mark devices, systems, and equipment according
to the standards of safety technology. In addition, these persons must be familiar with all
warning instructions and maintenance measures in this text.
Disregarding this warning may result in damage to equipment and/or serious personal
injury.
Summary of Contents for 1108712
Page 1: ...User manual UM EN GW PN DP1E 1DB9 Protocol converter for PROFINET to PROFIBUSDP ...
Page 8: ...GW PN DP 1E 1DB9 8 34 PHOENIX CONTACT 4063_en_B ...
Page 12: ...GW PN DP 1E 1DB9 12 34 PHOENIX CONTACT 4063_en_B ...
Page 26: ...GW PN DP 1E 1DB9 26 34 PHOENIX CONTACT 4063_en_B ...
Page 28: ...GW PN DP 1E 1DB9 28 34 PHOENIX CONTACT 4063_en_B ...
Page 30: ...GW PN DP 1E 1DB9 30 34 PHOENIX CONTACT 4063_en_B ...
Page 32: ...GW PN DP 1E 1DB9 32 34 PHOENIX CONTACT 4063_en_B ...