PFT G 5 c FU 230V
Operating Manual
Issued: 09.2007
Knauf PFT GmbH & Co. KG
52
Parameter settings for the Yaskawa type 606 V7 frequency converter
Parameter Function
Setting
Notes
001
Password
0
When adjusting parameters,
set to 4, then to 0
002
Selection of control type
0
003 Selection
of
operational
reference value
1
005
Selection of shutdown procedure
1
008
Selection of frequency reference
value
1
011
Maximum output frequency
70
Hz
012 Maximum
voltage
230 V
014
Mean output frequency
10
Hz
015
Mean output frequency voltage
48
V
016
Minimum output frequency
1.5
Hz
019
Acceleration time 1
2.5
sec.
020
Deceleration time 1
0
021
Acceleration time 2
0
022
Deceleration time 2
0
024
Fixed reference value 1
46
Hz (new motor 401 rpm)
025
Fixed reference value 2
50
Hz
031
Fixed reference value 8
14.88
Hz
034
Fixed reference value lower limit
43
%
036
Motor nominal current
14.9
A (for 4 kW motor)
037
Electronic thermal protection
0
On
038
Thermal protection triggers after
1 min.
039 Fan
1 Continuous
operation
058
Multi-function output selection 2
4
090
Time for stop
0.5
sec.
093
Current limiting during
acceleration
190 %
095
Frequency detection level
30
Hz
105 Torque
compensation
25
106
Nominal slip of motor
3.3
Hz
Summary of Contents for G 5 c FU
Page 50: ...PFT G 5 c FU 230V Operating Manual Issued 09 2007 Knauf PFT GmbH Co KG 50 Circuit diagram...
Page 51: ...PFT G 5 c FU 230V Operating Manual Issued 09 2007 Knauf PFT GmbH Co KG 51 Circuit diagram...
Page 53: ...PFT G 5 c FU 230V Operating Manual Issued 09 2007 Knauf PFT GmbH Co KG 53...
Page 55: ...PFT G 5 c FU 230V Operating Manual Issued 09 2007 Knauf PFT GmbH Co KG 55...