81
7.4.1.10 Indoor units mode conflict
Error Code
P5(old model) or - -(new model)
Malfunction conditions
The indoor units cannot work cooling mode and heating at same time.
Heating mode has a priority.
Potential causes
●
Suppose Indoor unit A working in cooling mode or fan mode, and
indoor unit B is set to heating mode, then A will change to off and
B will work in heating mode.
●
Suppose Indoor unit A working in heating mode, and indoor unit
B is set to cooling mode or fan mode, then B will change to stand
by and A will be no change.
Cooling mode
Heating Mode
Fan
Off
Cooling mode
No
Yes
No
No
Heating Mode
Yes
No
Yes
No
Fan
No
Yes
No
No
Off
No
No
No
No
No: No mode conflict;
Yes: Mode conflict
Summary of Contents for 3PAMS18-HH-MZO2
Page 5: ...4 ...
Page 29: ...28 3PAMSH18 MZO2 5 ...
Page 30: ...29 6 2 Wiring diagram of 1 drive 3 outdoor M3OF 27HFN1 M ...
Page 31: ...30 3PAMSH27 MZO3 3PAMS27 HH MZO3 ...
Page 32: ...31 M3OH 27HFN1 M ...
Page 33: ...32 6 3 Wiring diagram of 1 drive 4 outdoor M4OF 36HFN1 M ...
Page 34: ...33 M4OH 36HFN1 M 3PAMSH36 MZO4 ...
Page 36: ...35 6 4 Wiring diagram of 1 drive 5 outdoor M5OF 48HFN1 M ...
Page 47: ...46 PCB board of M5OF 48HFN1 M M4OH 36HFN1 M ...
Page 51: ...50 PCB Board of 3PAMS48 HH MZO5 3PAMS36 HH MZO4 3PAMSH48 MZO5 ...
Page 53: ...52 IPM board of 3PAMS48 HH MZO5 3PAMS36 HH MZO4 3PAMSH48 MZO5 ...
Page 72: ...71 Operating els Standby Pic 2 IPM for 2 zone 3 zone ...
Page 91: ...90 Operating els Standby Pic 2 IPM board for 2 zone 3 zone ...
Page 93: ...92 PIC 4 Check point button press 1 time for check how many indoor units are connected ...
Page 99: ...98 IPM board for 4 zone ...
Page 103: ...102 Two ports of the inductance Inductance ...
Page 106: ...105 Vs Vcc Vsp FG ...
Page 110: ...109 ...
Page 113: ...112 ...
Page 116: ...115 ...
Page 120: ...119 Faulty outdoor PCB Trouble shooting ...
Page 129: ...128 ...
Page 136: ...135 Red Blue Red Yellow Brown Orange ...
Page 137: ...136 Brown White ...