5. Electronic Function
5.1 Abbreviation
T1: Indoor ambient temperature
T2: Middle indoor heat exchanger coil
temperature
T2B: Indoor heat exchanger exhaust coil
temperature (located on the outdoor unit)
T3: Outdoor heat exchanger pipe temperature
T4: Outdoor ambient temperature
T5: Compressor discharge temperature
5.2 Electric Control Working Environment.
5.2.1 Input voltage: 230V.
5.2.2 Input power frequency: 60Hz.
5.2.3 Indoor fan standard working amp.: <1A
5.2.4 Outdoor fan standard working amp.: <1.5A.
5.2.5 Four-way valve standard amp.: <1A.
5.3 Main Protection
5.3.1 Compressor Restart Delay
---- The compressor takes 1 minute to start up the
first time. Further restarts take 3 minutes.
5.3.2 Temperature Protection of Compressor
Discharge.
When
the
discharge
temperature
of
the
compressor rises, the running frequency is limited
according to the following rules:
----If 10
5
℃
(
221
℉
)
≦
T5<
110
℃
(230
℉
), maintain
the current frequency.
----If the temperature increase and T5
≧
110
℃
(
230
℉
), decrease the frequency to a lower level
every 2 minutes till to F1.
---If T5
≧
115
℃
(
239
℉
) for 10 seconds, the
compressor stops and then restart until T5<90
℃
(194
℉
).
5.3.3 Fan Speed Malfunction
---- If outdoor fan speed is lower than
100RPM
or
higher than 2400RPM for 60 seconds or more,
the unit stops and LED displays failure code.
5.3.4 Inverter Module Protection.
---- The inverter protection module ensures that
faults related to current, voltage, or temperature
does not damage the inverter.
If these protections are triggered, the A/C unit
stops and the LED displays the failure code.
The unit restarts 3 minutes after the protection
mechanism has turned off.
5.3.5 Low Voltage Protection
VOLTAGE
No limit
VOLT_LTM_FREQ1_ADD
VOLT_LTM_FREQ2_ADD
Note: If low voltage protection triggers and
voltage is not restored to normal within 3
minutes, the protection remains active even
after a machine restart.
5.3.6 Compressor Current Limit Protection
The temperature interval for the current limit is
the same as the range of the T4 frequency limit.
Cooling mode:
Summary of Contents for 3PAMS18-HH-MZO2
Page 5: ...4 ...
Page 29: ...28 3PAMSH18 MZO2 5 ...
Page 30: ...29 6 2 Wiring diagram of 1 drive 3 outdoor M3OF 27HFN1 M ...
Page 31: ...30 3PAMSH27 MZO3 3PAMS27 HH MZO3 ...
Page 32: ...31 M3OH 27HFN1 M ...
Page 33: ...32 6 3 Wiring diagram of 1 drive 4 outdoor M4OF 36HFN1 M ...
Page 34: ...33 M4OH 36HFN1 M 3PAMSH36 MZO4 ...
Page 36: ...35 6 4 Wiring diagram of 1 drive 5 outdoor M5OF 48HFN1 M ...
Page 47: ...46 PCB board of M5OF 48HFN1 M M4OH 36HFN1 M ...
Page 51: ...50 PCB Board of 3PAMS48 HH MZO5 3PAMS36 HH MZO4 3PAMSH48 MZO5 ...
Page 53: ...52 IPM board of 3PAMS48 HH MZO5 3PAMS36 HH MZO4 3PAMSH48 MZO5 ...
Page 72: ...71 Operating els Standby Pic 2 IPM for 2 zone 3 zone ...
Page 91: ...90 Operating els Standby Pic 2 IPM board for 2 zone 3 zone ...
Page 93: ...92 PIC 4 Check point button press 1 time for check how many indoor units are connected ...
Page 99: ...98 IPM board for 4 zone ...
Page 103: ...102 Two ports of the inductance Inductance ...
Page 106: ...105 Vs Vcc Vsp FG ...
Page 110: ...109 ...
Page 113: ...112 ...
Page 116: ...115 ...
Page 120: ...119 Faulty outdoor PCB Trouble shooting ...
Page 129: ...128 ...
Page 136: ...135 Red Blue Red Yellow Brown Orange ...
Page 137: ...136 Brown White ...