18
from the vacuum pump to the valve at the bottom
of the cylinder. If the refrigerant is R410A, make
the cylinder bottom up to ensure liquid charge.
2). Purge the air from the charge hose
Open the valve at the bottom of the cylinder and
press the check valve on the charge set to purge
the air (be careful of the liquid refrigerant).
3) Put the charging cylinder onto the electronic
scale and record the weight.
4). Open the valves (Low side) on the charge set
and charge the system with liquid refrigerant
If the system cannot be charge with the specified
amount of refrigerant, or can be charged with a
little at a time (approximately 150g each time) ,
operating the air conditioner in the cooling cycle;
however, one time is not sufficient, wait
approximately 1 minute and then repeat the
procedure.
5).When the electronic scale displays the proper
weight, disconnect the charge hose from the 3-
way valve’s service port immediately
If the system has been charged with liquid
refrigerant while operating the air conditioner, turn
off the air conditioner before disconnecting the
hose.
6). Mounted the valve stem caps and the service
port. Use torque wrench to tighten the service
port cap to a torque of 18N·m (13.27 ft·lbs).
Always leak check after servicing the refrigerant
system.
For M3OF-27HFN1-M/M4OF-36HFN1-M/M5OF-
48HFN1-M/M2OH-18HFN1-M/M3OH-27HFN1-M/
M4OH-36HFN1-M/
3PAMS48-HH-MZO5
There are one low-pressure centralized valve and
one high-pressure centralized valve, it will be
more time saving when vacuum and recycle
refrigerant. But refer to the previous instruction
when vacuum and recycle refrigerant.
Summary of Contents for 3PAMS18-HH-MZO2
Page 5: ...4 ...
Page 29: ...28 3PAMSH18 MZO2 5 ...
Page 30: ...29 6 2 Wiring diagram of 1 drive 3 outdoor M3OF 27HFN1 M ...
Page 31: ...30 3PAMSH27 MZO3 3PAMS27 HH MZO3 ...
Page 32: ...31 M3OH 27HFN1 M ...
Page 33: ...32 6 3 Wiring diagram of 1 drive 4 outdoor M4OF 36HFN1 M ...
Page 34: ...33 M4OH 36HFN1 M 3PAMSH36 MZO4 ...
Page 36: ...35 6 4 Wiring diagram of 1 drive 5 outdoor M5OF 48HFN1 M ...
Page 47: ...46 PCB board of M5OF 48HFN1 M M4OH 36HFN1 M ...
Page 51: ...50 PCB Board of 3PAMS48 HH MZO5 3PAMS36 HH MZO4 3PAMSH48 MZO5 ...
Page 53: ...52 IPM board of 3PAMS48 HH MZO5 3PAMS36 HH MZO4 3PAMSH48 MZO5 ...
Page 72: ...71 Operating els Standby Pic 2 IPM for 2 zone 3 zone ...
Page 91: ...90 Operating els Standby Pic 2 IPM board for 2 zone 3 zone ...
Page 93: ...92 PIC 4 Check point button press 1 time for check how many indoor units are connected ...
Page 99: ...98 IPM board for 4 zone ...
Page 103: ...102 Two ports of the inductance Inductance ...
Page 106: ...105 Vs Vcc Vsp FG ...
Page 110: ...109 ...
Page 113: ...112 ...
Page 116: ...115 ...
Page 120: ...119 Faulty outdoor PCB Trouble shooting ...
Page 129: ...128 ...
Page 136: ...135 Red Blue Red Yellow Brown Orange ...
Page 137: ...136 Brown White ...