23
℃
34
33
Standby
28
27
Fmax=T4FREHEATMAX1
25
24
Fmax=T4FREHEATMAX2
22
21
Fmax=T4FREHEATMAX3
19
18
Fmax=T4FREHEATMAX4
17
16
Fmax=T4FREHEATMAX5
15
14
Fmax=T4FREHEATMAX6
12
11
Fmax=T4FREHEATMAX7
6
5
Fmax=T4FREHEATMAX8
1
0
Fmax=T4FREHEATMAX9
-3
-4
Fmax=F21
-7
-8
Fmax=F22
-11
-12
Fmax=F23
-15
-16
Fmax=F24
Fmax=F25
5.4.2 Defrosting Control
Conditions for Defrosting:
After the compressor starts and enters normal
operation, mark the minimum value of T3 from
the 10th to 15th minute as T30.
If any one of the following conditions is satisfied,
the unit enters defrosting mode:
1) If the compressor
’s cumulative running time
reaches 29 minutes and T3< TCDI1 and T3
+
T30SUBT3ONE
≦
T30.
2) If the compressor cumulative running time
reaches 35 minutes and T3< TCDI2 and T3
+
T30SUBT3TWO
≦
T30.
3) If the compressor cumulative running time
reaches 40 minutes and T3< -24C for 3 minutes.
4) If the compressor cumulative running time
reaches 120 minutes and T3<-15
℃
.
5) If the air conditioner is shut down from heating
mode, it will enter defrost if any of the following
conditions are met (this condition can be shielded
by parameters):
a) The continuous operation time of the press
exceeds 30 minutes, and T3<-7 degrees;
b) The continuous operation time of the press
is more than 30 minutes, and T30<-15 degrees;
6) For the first defrosting when the machine is
turned on, after the compressor has been running
for 30 minutes, when T4-T3> (0.5T4 +
KDELTT_ADD) and T3 <TCDIN5_ADD, it will
immediately enter the defrosting action. After
performing this defrosting action once, this rule
will be invalid until the next restarting operation.
7) If any one of the following conditions is
satisfied, the unit enters defrosting mode,
a) If T3 or T4 is lower than -3°C for 30
seconds,Ts-T1 is lower than 5°C and compressor
running time is more than
DEFROST_COND6_IN_TIM.
b) If T3 or T4 is lower than -3°C for 30 seconds
and compressor running time is more than
DEFROST_COND6_30.
Defrost Stop Conditions
If any one of the following conditions is satisfied,
defrosting ends and the unit returns to normal
heating mode:
----T3 rises above than TCDE1
℃
.
----T3 remains at TCDE2
℃
or above for 80
seconds.
----The machine runs for 10 consecutive minutes
in defrosting mode.
Defrosting Action
:
Summary of Contents for 3PAMS18-HH-MZO2
Page 5: ...4 ...
Page 29: ...28 3PAMSH18 MZO2 5 ...
Page 30: ...29 6 2 Wiring diagram of 1 drive 3 outdoor M3OF 27HFN1 M ...
Page 31: ...30 3PAMSH27 MZO3 3PAMS27 HH MZO3 ...
Page 32: ...31 M3OH 27HFN1 M ...
Page 33: ...32 6 3 Wiring diagram of 1 drive 4 outdoor M4OF 36HFN1 M ...
Page 34: ...33 M4OH 36HFN1 M 3PAMSH36 MZO4 ...
Page 36: ...35 6 4 Wiring diagram of 1 drive 5 outdoor M5OF 48HFN1 M ...
Page 47: ...46 PCB board of M5OF 48HFN1 M M4OH 36HFN1 M ...
Page 51: ...50 PCB Board of 3PAMS48 HH MZO5 3PAMS36 HH MZO4 3PAMSH48 MZO5 ...
Page 53: ...52 IPM board of 3PAMS48 HH MZO5 3PAMS36 HH MZO4 3PAMSH48 MZO5 ...
Page 72: ...71 Operating els Standby Pic 2 IPM for 2 zone 3 zone ...
Page 91: ...90 Operating els Standby Pic 2 IPM board for 2 zone 3 zone ...
Page 93: ...92 PIC 4 Check point button press 1 time for check how many indoor units are connected ...
Page 99: ...98 IPM board for 4 zone ...
Page 103: ...102 Two ports of the inductance Inductance ...
Page 106: ...105 Vs Vcc Vsp FG ...
Page 110: ...109 ...
Page 113: ...112 ...
Page 116: ...115 ...
Page 120: ...119 Faulty outdoor PCB Trouble shooting ...
Page 129: ...128 ...
Page 136: ...135 Red Blue Red Yellow Brown Orange ...
Page 137: ...136 Brown White ...