TTR-04CW Electromechanical Tripod Turnstile
9.4 Actions in emergency
For urgent evacuation of people from business facilities in case of fire, natural calamities
and other emergencies, the additional emergency exit should be provide.
To provide unobstructed and fast escape routes in emergency cases through
the turnstile, the key override control is used. The sequence of actions is described in
Clause 5.10 of the Manual.
Also the turnstile can be opened with a command sent from the
Fire Alarm
emergency
unblocking device. The procedure is described in Clause 5.8 of the Manual.
9.5 Troubleshooting
Possible faults, which can be cleared by the users themselves, are listed in Table 4. All
other faults shall be cleared by the Manufacturer or his representatives only.
Table 4. Possible faults and remedy
Fault
Possible
cause
Remedy
At the power-up
the turnstile won’t work,
and there is no light
indication on the turnstile
housing and the RC panel
No supply
voltage to
the CLB
Switch off the turnstile power supply from the AC
mains, open the turnstile housing cover,
and remove the outer panel. Check the power
cable serviceability and reliability of its connection
to the CLB
XT3
connector block
The turnstile
is not controlled
in one of the directions,
and there is light
indication on the turnstile
housing and on the RC
panel
The CLB
does not
receive
a control
signal from
this direction
Switch off the turnstile power supply from the AC
mains, open the turnstile housing cover,
and remove the outer panel. Check the RC panel
/ WRC kit / ACS controller cable serviceability and
reliability of its connection to the CLB
XT1
.
L
and
XT1
.
H
connector blocks
25
Summary of Contents for TTR-04CW
Page 1: ...ASSEMBLY AND OPERATION MANUAL TTR 04CW Electromechanical Tripod Turnstile...
Page 2: ...Electromechanical Tripod Turnstile TTR 04CW Assembly and Operation Manual...
Page 11: ...Assembly and Operation Manual Figure 6 Connection layout 10...
Page 31: ......
Page 32: ......
Page 34: ...www perco com...