background image

Assembly and Operation Manual 

5.5.3 Control over the turnstile is effected by input of the control signal to the turnstile at 
both control modes. The passage waiting time in the pulse control mode is 5 seconds 
regardless of the control signal length. In the potential control mode the passage waiting 
time equals the length of the control signal. 

5.5.4 The pulse control mode is intended for the turnstile operation from the RC panel, the 
WRC or the ACS controller,

 

outputs of which support the pulse control mode. 

Standard control inputs: 

Unlock A

Stop

 and 

Unlock B

Special control input:  

Fire Alarm

See Table 2 for the turnstile operating modes at this control mode. The algorithm of control 
signals at this mode is stipulated in Appendix A. 

The minimum input signal duration, when the operating mode can be changed, should be 
100 msec. The passage waiting time is 5 sec. and it does not depend on the input signal 
duration. 

See Clause 5.9.3.1 for the turnstile operation at special 

Fire Alarm

 control input. 

5.5.5 The potential control mode is intended for the turnstile operation from the ACS 
controller,

 

outputs of which support the potential control mode

 

(for example,

 

a lock 

controller). 

Standard control inputs: 

Unlock A

 and 

Unlock B

Special control inputs: 

Stop

 and 

Fire Alarm

See Table 3 for the turnstile operating modes at this control mode. The algorithm of control 
signals at this mode is stipulated in Appendix B. 

The minimum input signal duration, when the operating mode can be changed, should be 
100 msec. The passage waiting time is equal to the low-level signal duration (the turnstile 
remains open in the set direction if a low-level signal exists at the set direction input by the 
moment of passage). 

At the low-level signal inputting to the 

Stop

 input,

 

both directions are locked for the time of 

the signal duration regardless the signal strength at the inputs

 

Unlock A

 and 

Unlock B.

 At 

the low-level signal removing from the 

Stop

 input, the directions are set to the control 

mode according to the signal strength at the inputs

 

Unlock A

 and 

Unlock B

See Clause 5.9.3.2 for the turnstile operation at the special Fire Alarm control input. 

5.6  Operation with RC panel 

5.6.1 When the buttons on the RC panel are pressed (the

 STOP

 button and the two other 

buttons corresponding to the passage direction), the closing of the relevant contact 

Unlock 

A

Stop

 or 

Unlock B

 to the contact 

GND

 occurs (i.e. forming 

 

of the low-level signal relatively to the contact

 GND

). 

5.6.2 

Operation logic of the turnstile at the single passage in the A(B) direction 

 

at the pulse control mode: 

5.6.2.1 When the button, corresponding to the A(B) passage direction, is pressed 
on the RC panel,

 

the closing of the contact

 

Unlock

 

A(B)

 

to the contact

 

GND

 

occurs 

(i.e. forming of the low-level signal on the contact 

Unlock A(B)

 relatively to the 

contact 

GND

). 

5.6.2.2 The CLB microcontroller processes the incoming command and generates 
the command to the control mechanism, which opens the A(B) passage direction 
(lifts the upper (lower) edge of the key holt). 

14 

Summary of Contents for TTR-04CW

Page 1: ...ASSEMBLY AND OPERATION MANUAL TTR 04CW Electromechanical Tripod Turnstile...

Page 2: ...Electromechanical Tripod Turnstile TTR 04CW Assembly and Operation Manual...

Page 3: ...ide control 17 5 11 Operation contingencies and response 17 6 MARKING AND PACKAGING 18 7 SAFETY REQUIREMENTS 18 7 1 Installation safety requirements 18 7 2 Operation safety requirements 18 8 INSTALLAT...

Page 4: ...ties banks administrative buildings retail outlets railway terminals airports etc To ensure fast and convenient passage it is recommended to install one turnstile per 500 people working the same shift...

Page 5: ...8 5 of the heating system with thermocontrol max 60 Throughput rate in the single passage mode 30 persons min in a free passage mode 60 persons min Passageway width 600 mm Barrier arm rotation force m...

Page 6: ...ertificate 1 Operation manual 1 Packaging Box 1 4 2 Optional equipment supplied on request Turnstile power supply 1 Power supply of the heating system 24 ACV 1 WRC kit2 1 Intrusion detector 1 Siren fo...

Page 7: ...M8 for mounting the barrier arm 7 AC power cables1 8 turnstile power supply unit1 9 turnstile power cable1 10 RC panel WRC1 ACS controller 1 11 cable of the RC panel WRC ACS controller 1 12 anchor bol...

Page 8: ...ing to ensure accurate count of inputs to an ACS The turnstile is supplied with safe voltage maximum 14 V with the heating system with thermocontrol in operation no more than 40 V The turnstile has lo...

Page 9: ...e RC panel is connected to the CLB with a multicore cable 11 via the XT1 L connector block See Fig 4 Figure 4 RC panel overall view 1 2 3 buttons LEFT RIGHT STOP for setting the passage mode 4 5 green...

Page 10: ...tains X1 Control connector to connect the control mechanism connected to the X1 connector of the control mechanism with the turnstile cable XT1 L In connector block to connect the RC panel WRC inputs...

Page 11: ...Assembly and Operation Manual Figure 6 Connection layout 10...

Page 12: ...ove devices can be connected to the turnstile as follows any device separately in any combination with each other all devices simultaneously in parallel Note At the parallel connection of the above de...

Page 13: ...re Alarm contact relatively to the GND contact As the control element there can be used a normally closed relay contact or a circuit with open collector output at that Fig 7 and 8 Note For generating...

Page 14: ...f the turnstile control a pulse control mode and a potential control mode They determine available operating modes of the turnstile Table 2 and Table 3 5 5 2 The control mode is set by the jumper on t...

Page 15: ...dix B The minimum input signal duration when the operating mode can be changed should be 100 msec The passage waiting time is equal to the low level signal duration the turnstile remains open in the s...

Page 16: ...peration with ACS controller 5 8 1 In the pulse control mode control over the turnstile with an ACS controller is similar to that with the RC panel 5 8 2 In the potential control mode control over the...

Page 17: ...signal absence Other control commands are ignored at that When the low level signal appears at the Fire Alarm input the turnstile turns to the Always locked mode 5 9 3 2 In the potential control mode...

Page 18: ...ial signal Ready is generated in each of the above cases 5 11 2 2 In case of unauthorized access the Ready signal is formed as follows at 8 arm rotation one of the optical sensors Fig 13 responds and...

Page 19: ...the turnstile Chapter 4 1 is packed in a transportation box which keeps it undamaged during the transportation and storage Box overall dimensions length width height 114 32 32 cm Gross weight max 42 k...

Page 20: ...ccount that the resetting device operates as follows at the barrier arm turning at the angle of more than 60 the reset is effected in the direction of movement at the barrier arm turning at the angle...

Page 21: ...he CLB connectors location is shown in Fig 5 Cables parameters and their length are given in clause 8 3 The installation surface and passage area recommendations are given in clause 8 1 1 Unpack the t...

Page 22: ...horizontal plane using hook and loop cable ties 14 Connect S1 and S2 cable connectors connecting the indication board of the cover with the board in the housing Mount the cover with LED indication ba...

Page 23: ...the heating and the temperature indication turns off 4 Check operation of the intrusion detector and siren if included in the delivery set and installed accordingly After the power up wait until the m...

Page 24: ...arrow pictograms left and right are on The turnstile is locked in the direction of completed passage 4 Free passage in the set direction open for free passage in the chosen direction Press the STOP bu...

Page 25: ...h for entry and exit The high level on contacts Unlock A and Unlock B or low level on the contact Stop The red indicator above the STOP button is on The Red cross pictogram is on The turnstile is lock...

Page 26: ...anufacturer or his representatives only Table 4 Possible faults and remedy Fault Possible cause Remedy At the power up the turnstile won t work and there is no light indication on the turnstile housin...

Page 27: ...he rotation axis of the pusher two on the fastening axis of the springs holes in the fastening parts of the springs lock cylinder of the mechanical lock 15 through the keyhole Note Avoid the ingress o...

Page 28: ...and transportation the boxes can be stacked no more than 4 layers high The storage of the turnstile is allowed indoors at ambient temperature from 40 C to 50 C and at relative air humidity up to 75 at...

Page 29: ...e passage has been effected in this direction or until the command Always locked and the status of passage direction A does not change The command is ignored if at the moment of its receipt the status...

Page 30: ...ons close at this command Direction A is open open for passage in direction A There is a low level at contact Unlock A while a high level is present at contacts Stop and Unlock B At this command direc...

Page 31: ......

Page 32: ......

Page 33: ...PERCo Polytechnicheskaya str 4 block 2 194021 Saint Petersburg Russia Tel 7 812 247 04 64 E mail export perco com support perco com www perco com...

Page 34: ...www perco com...

Reviews:

Related manuals for TTR-04CW