Assembly and Operation Manual
If the turnstile is locked (the “Always locked” mode /“Both directions closed” mode when
both directions are locked, Tables 2 and 3) and a signal comes from the intrusion detector,
the “Alarm” signal is generated. The “Alarm” signal is disabled after 5 sec. or by executing
of any received command.
The signal from the intrusion detector is ignored for the period
of authorized unlocking of the turnstile in either or both directions.
If within 3 sec. after the “Always locked”/“Both directions closed” mode is set, the signal
from the intrusion detector comes, it is also ignored.
The intrusion detector status signal is constantly transmitted to the
Det Out
and
Common
contacts of the CLB
XT1.H
5.9.3 The emergency unblocking device is connected to the
XT1.L
connector block of the
CLB in accordance with the connection layout (Fig. 5 and 6). If the
Fire Alarm
input is not
used, it is necessary to set a jumper between the contacts
Fire Alarm
and
GND
. This
jumper is preset at the factory.
Operation of the turnstile under commands of the emergency unblocking device:
5.9.3.1 In the pulse control mode, when a low-level signal is removed from the
Fire
Alarm
input, both passage directions become open for the whole period of the
signal absence. Other control commands are ignored at that. When the low-level
signal appears at the
Fire Alarm
input, the turnstile turns to the “Always locked”
mode.
5.9.3.2 In the potential control mode, when a low-level signal is removed from the
Fire Alarm
input, both passage directions become open for the whole period of the
signal absence. Other controlling commands are ignored at that. When the low-level
signal appears at the
Fire Alarm
input, the passage directions turn to the mode in
accordance with the signal levels at the inputs
Unlock
A
,
Unlock B
and
Stop
.
5.9.4 The remote indicators are connected to the connector blocks
XT4
(Light A) and
XT5
(Light B). At that the “Light A” (“Light B”) relay is active (the voltage is supplied to the relay
coil), when the “Green arrow” pictogram on the LED indication display, corresponding to
the set passage direction, lights, and it is passive, when the “Green arrow” pictogram on
the Led display does not light. The response/release of the relays “Light A” and “Light B”
can be defined according to lighting up/going down of the red indicators, which are
installed near the above mentioned relays (Fig. 5). Output cascades for the “Light A” and
the “Light B” relays are nonbridging relay contacts (Fig. 10) with the following signal
characteristics:
maximum switched voltage ......................................................................... 30V DC;
maximum switched voltage .......................................................................... 42V AC;
maximum switched AC/DC ................................................................................. 3 A;
closed contact resistance ................................................... no more than 0.15 Ohm.
Figure 10. Output cascades for Light A and Light B
16
Summary of Contents for TTR-04CW
Page 1: ...ASSEMBLY AND OPERATION MANUAL TTR 04CW Electromechanical Tripod Turnstile...
Page 2: ...Electromechanical Tripod Turnstile TTR 04CW Assembly and Operation Manual...
Page 11: ...Assembly and Operation Manual Figure 6 Connection layout 10...
Page 31: ......
Page 32: ......
Page 34: ...www perco com...