background image

User Manual 

 

On the page, you can select following: 

1.  The title bar if he page contains 

PERCo

 trademark and buttons to select the language 

of Web-interface. By clicking on the 

PERCo

 company logo you navigate to the main 

page from other sections of Web-interface. 

2.  Sidebar of the Web-interface navigation. The panel has the following structure 

“Network”  

“Password”  

“Time”  

“Settings” 

“Memory usage” 

 

“Template”  

“Operation devices” 

“Physical contacts” 

“Readers” 

“Card format” 

“Configuration” 

“Edit” 

“Internal responses” 

“Operating device control” 

 

 

“Input”  

“List”  

“Access cards” 

“Load from file” 

 

“Events”    

“Status”    

“Diagnostic”  

 

3.  Working area of the page. 

26 

Summary of Contents for CL-05.2

Page 1: ...Lock Controller CL 05 2 OPERATION MANUAL ...

Page 2: ...Lock Controller CL 05 2 Operation Manual ...

Page 3: ...ss setting method 9 6 MARKING AND PACKAGING 10 7 SAFETY REQUIREMENTS 10 7 1 Installation safety 10 7 2 Operation safety 10 8 INSTALLATION 11 8 1 General instructions 11 8 2 Cables 11 8 3 Installation order 11 8 4 Powering 16 8 5 Connection via Ethernet network 16 9 CONFIGURATION 16 10 FIRMWARE UPDATE 16 11 OPERATION 17 11 1 ACM when operating as a part of ACS 17 11 2 Indication 19 11 3 Troubleshoo...

Page 4: ... having two controllers of this model installed entrance point Controller features built in HID and EM Marine proximity card reader and is able to control one electromagnetic or electromechanical lock Note Having two CL 05 2 lock controllers installed for managing one two way entrance point it is necessary to use normally closed opened when energized electromechanical locks as operation unit Elect...

Page 5: ... Note Possible options for allocating memory see Appendix 2 Clause 3 4 50 000 cards and 230 000 events set by default 40 000 cards and 390 000 events 30 000 cards and 550 000 events 20 000 cards and 710 000 events 10 000 cards and 870 000 events Number of additional outputs 2 1 Mean lifetime 8 years Electric shock protection class III under GOST R IEC 730 1 94 Housing protection class IP54 under E...

Page 6: ... 4 Package 1 Certificate 1 Operation manual 1 4 2 Additional equipment supplied upon request Power supply unit 1 PoE splitter 1 1 1 PoE splitter allows controller powering via Ethernet network Splitter can be used with network commutators supporting power transmission technology through PoE twisted pair cable and is compatible with IEEE 802 3af standard 5 ...

Page 7: ...races lock circuit condition which allows omitting door sensor reed switch use Door sensor is replaced by the lock terminal block Controller allows lock operation with the following devices RC button Exit proximity card presented to the controller computer when connected via Ethernet network and at the Software installation emergency unlocking device Fire Alarm Apart from this it is possible to co...

Page 8: ...stics control element relay contact minimal commutated current max 1 mA closed contact resistance considering connection cable resistance max 300 Ohm control element scheme with open collector output closed contact voltage low level signal on controller input max 0 8 V Note All the unconnected inputs are pulled to the power supply In order to create a high level signal all the input contacts Door ...

Page 9: ...sed for connecting emergency unlocking device Fire Alarm Connection scheme is given on Fig 3 Normally open relay contact or a scheme with open collector output can serve as a control element Input signal parameters are the same as stated for Door and DU inputs Section 5 3 Sending control signal from Fire Alarm emergency unlocking device connected to the controller on the input OD gets unlocked and...

Page 10: ... Note Controller network settings change is possible only from the PC through the Web interface or from the Software At that the controller and the PC are to be in one subnet 2 IP MODE 1 2 jumper position This mode is aimed at operation in networks with IP address dynamic allocation At that the controller gets the IP address gateway subnet mask from DHCP network server 3 IP DEFAULT 2 3 jumper posi...

Page 11: ... out by qualified specialists who have studied this Manual Attention Controller connection and jumper installation should be carried out with de energized equipment and disconnected power supplies Cabling should be executed with the general electrical and work safety rules observance Controller installation should be carried out by fault free instruments only Power supply installation safety requi...

Page 12: ...commended to install controller at least 1 meter apart from any other external readers and other EMI sources EMI sources may reduce proximity card reading distance and be the cause of system operation malfunctions The sources of electromagnetic interferences are readers AC lines electric generators electric motors AC relays thyristor light regulators PC displays computer and telephone signal commu...

Page 13: ...s case 9 Prepare door for lock installation and install the lock in accordance with its operation documentation Connect cable 3 FIg 3 Table 3 to the lock 10 Ground lock housing or its locking plate in order to protect it from static electricity If the lock is installed on the metal door ground the door leaf Grounding is to be performed with a wire of minimum 0 75 mm2 cross section 11 Set the RC bu...

Page 14: ...ontroller power connection through PoE splitter is given in Appendix 1 17 Install power supply to its permanent operation position Connect cable 2 Fig 3 Table 3 to the power supply and to the controller 18 Lay and fix cables using plastic staples e g SC4 6 SC5 7 SC7 10 During cable installation and cable laying it is necessary to consider the requirements given in Section 8 2 19 Check lack of brea...

Page 15: ...Operation Manual Figure 3 Controller connection scheme 14 ...

Page 16: ...he given scheme features connection of locks open when energized normally closed electromechanical locks In order to connect locks open when de energized normally open electromechanical locks and electromagnet locks install the supplementary relay with normally closed contacts connected to the lock power supply circuit 15 ...

Page 17: ...d services as DNS and WINS are not required Controller is to be connected to the same network segment or directly to the computer network card output When connection is made all the network settings of the controller can be changed to the ones recommended by the system administrator from the Software or through Web interface 9 CONFIGURATION Controller configuration access cards transfer to the con...

Page 18: ...ecomes available when controller is connected to the network and when connection with other system controllers is provided Connecting to the PC with Local Software installed Events from log event are automatically relocated into programme database each time the programme is initiated The data can be also relocated by clicking on the corresponding button in the programme Data on identifier owner fu...

Page 19: ...Off Off Control Off On Off Off Arming Off 1 Hz 1Hz Off No Closed Off Off On Off Open On Off Off 0 2 Control Card has no access rights Arming Any card Closed Off Off On 0 5 Open Control On Off Off 0 2 Card has access right Arming Off Off On 0 5 Open Control Card has access and arming disarming right Arming 1 On Off Off 0 2 At taking switch to Arming ACM Arming Off 1 Hz 1Hz 0 2 Open Repeated present...

Page 20: ...Faulty radio components on the controller board the controller needs repair at the manufacturer 11 3 2 Controller is not recognized by the PC Possible causes of the malfunction 1 No network settings in the computer set computer IP address and subnet mask Computer is to be connected either directly to the computer network card network connector or to the same Hub Switch to which the computer is con...

Page 21: ...rent ways look at the response time choosing the connection giving the quickest response time 6 Controller malfunctions Faulty operation of the elements providing connection via Ethernet IEEE 802 3 interface If controller does not detect connection to Ethernet connect it to the cable from which another controller operates If controller does not detect connection to Ethernet or connection with it c...

Page 22: ... controller surfaces Cleaning waste brush grainer No signs of dirt and damp 1 2 Remove covers from the power supply If there is a reserve power supply accumulator remove any dust dirt damp and oxides from the terminals Check the reserve power supply voltage If needed charge or change the battery Screwdriver cleaning waste brush grainer C4352 indicator Voltage is to comply with data given in the ba...

Page 23: ...rs output voltage is chosen with the switcher Operating with PERCo equipment it is necessary to turn the switcher into 12V mode Connection sequence Follow this sequence during controller connection through splitter 1 Choose splitter installation place Do not install splitter at more than 2 m distance from the controller 2 Connect Ethernet cable from controller to Con2 output of the splitter Table ...

Page 24: ...CL 05 2 Lock Controller Figure 5 Controller connection scheme through PoE splitter 23 ...

Page 25: ...ngs of memory allocation 28 4 CONFIGURATION 28 4 1 The choice of the controller configuration 28 4 2 Configuration of the Settings of the controller resources 29 4 2 1 Operating devices 29 4 2 2 Physical contacts inputs and outputs 30 4 2 3 Readers 31 4 2 4 The reading format of the card identifiers 31 4 2 5 Internal responses 31 5 CONTROL OF OPERATING DEVICE 32 6 ACCESS CARDS 33 6 1 Entering of t...

Page 26: ... and stopping the server of PERCo system 2 CONNECTION TO WEB INTERFACE OF THE CONTROLLER Connection between the controller and the computer is performed via Ethernet interface IEEE 802 3 Make sure that the computer and the controller are on the same subnet Ethernet It may become necessary to change network settings of the computer browser settings and to check operation of the network IP address o...

Page 27: ...te to the main page from other sections of Web interface 2 Sidebar of the Web interface navigation The panel has the following structure Network Password Time Settings Memory usage Template Operation devices Physical contacts Readers Card format Configuration Edit Internal responses Operating device control Input List Access cards Load from file Events Status Diagnostic 3 Working area of the page ...

Page 28: ...fields IP address Mask Gateway the new values of network Settings of the controller 3 Click Save button New network settings will be saved in the controller 3 2 Setting of the access password of the controller By default access password of the controller is not specified To change or set the new password 1 Click in the Web interface menu Settings Password The page with working area will be opened ...

Page 29: ... interface menu Settings Memory usage The page with working area will be opened 2 In dropdown list Memory resizing select one of the variants of the memory allocation 3 Click the Save button 4 CONFIGURATION 4 1 The choice of the controller configuration There is only one configuration template CL05 2 Controller available for CL 05 2 controller By default controller is configured according to this ...

Page 30: ...d window on the tabs General Alarm generator Reader 1 Operating device make the necessary changes of the Settings for corresponding resources Attention For the resource Reader 1 the parameter Card rights number indicates the number of the set of card rights used for passing with this reader By default value 1 is set everywhere for parameter Rights number and for correct operation of the controller...

Page 31: ...are available for setting and changing in future its functions Name in Web interface Function Wire color Input 1 Always Door sensor Door Pass white Input 2 Always RC button DU green Output 1 Always Lock operation Lock orange Input 3 Output 2 1 Input Fire Alarm 2 Output Alarm siren 3 Input output SYNC synchronization of 2 controllers brown Notes Input 3 or Output 2 of CL 05 2 controller are led in ...

Page 32: ...tention To avoid incorrect device operation do not change the settings of inbuilt reader 1 used for OD operation If necessary it is possible to restore to factory default settings by resetting configuration template see Clause 4 1 4 2 4 The reading format of the card identifiers Attention Change of this parameter when you have already entered the access control cards results in the passage on thes...

Page 33: ...nse Selector Receiver type specifies the controller response under condition of the responses launch Selector Response time and Response characteristics set corresponding Settings of the response 4 Click the Save button The window Internal response number will be closed the changed Settings will be passed to the controller 5 To remove the response from the list click the Delete button The window I...

Page 34: ...lick consistently in the Web interface menu Access cards Enter The page with working area will be opened 2 If necessary use the dropdown list in the heading of the Number type column select the format to display the cards identifiers Note The display format is not the format of reading of the card identifiers set in the Configuration section Clause 4 2 4 when you change the display format the form...

Page 35: ...the other cards 5 To transfer the entered card identifiers to the controller click the Save button in the working area of the page The identifiers will be transferred to the main list of the cards in section List Attention When you enter the card identifiers in the list of the controller by default they are granted rights of access over all ODs connected to the controller all 12 sets of rights for...

Page 36: ...ile button The cards will be saved in the file cards bin which can be used as a backup card list 4 To remove all the cards from the controller memory click the Clear log button 5 To change the Settings select one of the cards in the working area of the page The window of the identifier of the selected card opens 6 If necessary in the opened window on the Essential tab change the card Settings 7 Go...

Page 37: ... daily schedule flexible weekly schedule and transition from one set of time Settings to another set by changing his number The number of time criterion corresponds to order number of the set of Settings of time criterion in the network software 6 3 Loading the identifiers from a file Attention When loading the list of cards from the file to the controller previously loaded cards are deleted autom...

Page 38: ...ist Selected categories number put ticks the event categories which should be reported Following categories of events are available ID Card access Guard zone status change Guard zone resource state change Change input output state change Access without ID Card Functioning 5 Use the fields Range beginning point and Range end point to set the period of the report 6 Click the Apply button to apply th...

Page 39: ... testing the controller the event log is automatically cleared 3 For diagnostic purposes of the controller with the previous formatting click the Start button in the line Diagnostics formatting 15 min 4 To start formatting the internal memory of the controller click the Start button in the line Format 2 min In the confirmation window click OK Attention When formatting the controller memory the inf...

Page 40: ......

Page 41: ...PERCo Polytechnicheskaya str 4 block 2 194021 Saint Petersburg Russia Tel 7 812 247 04 64 E mail export perco com support perco com www perco com ...

Page 42: ...www perco com ...

Reviews: