AS-Interface
Diagnostics for AS-i Monitor and networking using AS-i Master
11.4.2.1 Status codes for the release circuits (OSSD)
11.4.2.2 Transparent output data
The transparent output data are available there to the safe unit as non-safe addi-
tional bits, for example for Start keys.
11.4.3
Acyclical data
Vendor Specific Object 1 – Analyzer status AS-i Circuit 1
Read only.
This object contains a bit pair for all 62 possible slaves which represents the sta-
tus of the slaves at this address:
Code bit [3..0] Status / color
Description
0
continuous green
Output on
1
flashing green
Wait time for Stop 1 in effect
2
continuous yellow
Startup / restart active
3
flashing yellow
External test required / acknowledgement /
Turn-on delay active
4
continuous red
Output off
5
flashing red
Fault
6
gray or off
Output not assigned
7 ... F
reserved
Tab. 11-11.
Information!
Monitors supporting less than 8 release circuits set all non-present release circuits to
“gray”.
Ch
2
15
2
14
2
13
2
12
2
11
2
10
2
9
2
8
2
7
2
6
2
5
2
4
2
3
2
2
2
1
2
0
0
reserved
Start2 EDM 2 Start1 EDM 1
Tab. 11-12.
Bit
Lamp color
11
red
10
yellow
01
green
00
no slave
Tab. 11-13.