Subject to reasonable modifications due to technical advances.
© Fuchs, Printed in Germany
13
Fuchs Group · Tel.: Germany (6 21) 7 76-0 · USA (3 30) 4 25 35 55 · Singapore 7 79 90 91
Internet http://www.pepperl-fuchs.com
Iss
u
e d
a
te
: 21
.1
0.2
011
AS-Interface
Spezifications
4.3
Safety-relevant characteristic data
4.3.1
Overview of parameter for determining the failure rates
Characteristic data
Value Standard
Safety category
4
EN 954-1
Safety category
4
EN ISO 13849-1: 2008
Performance Level (PL)
e
Safety Integrity Level (SIL)
3
EN 61508
Lifespan (TM) in years
20
EN ISO 13849-1: 2008
Maximum switch-on time in months
12
EN 61508
Max. system reaction time in
milliseconds
40
EN 61508
Tab. 4-2.
Attention!
In addition to the system reaction time of max. 40 ms, the reaction times of the safe AS-
interface sensor slave, of the sensor being used for monitoring, of the safe AS-interface
actuator slave and of the actuator used for this purpose must still be added. Please note
that additional reaction times may likewise arise through the configuration of the safety
monitor.
Notice!
Refer to the technical data for the slaves as well as to that for the sensors and actuators
for the reaction times to be added.
Attention!
The system reaction times of the daisy-chained AS-interface components are added up.
nop/y
switching intervals
t
cycle
[s]
B10d
value
electromechanics
Standard
MTTF
d
[years]
PFH [1/h]
105.120
300
2.500.000
237,82
9,908 x 10
-9
EN ISO
13849-1
52.560
600
475,65
4,853 x 10
-9
8.760
3600
2853,88
9,054 x 10
-10
Tab. 4-3.
nop/y
switching
intervals
t
cycle
B10d
value
electronics
PFH
electromechanics
PFH
total
Standard
MTTF
d
PFH
105.120
300
2.500.000
4,76 E
-09
237,82
1,12 x 10
-8
1,6 x 10
-8
EN 62061
EN 61508
52.560
600
475,65
5,09 x 10
-9
9,85 x 10
-9
8.760
3600
2853,88
7,82 x 10
-10
5,54 x 10
-9
Tab. 4-4.
Summary of Contents for VAS-2A1L-K31