AS-Interface
Function and startup of the Safety Monitor
For additional information, refer to the separate manual for the
ASIMON 3 G2
configuration software.
2.
Using a chip card with the master configuration
Configurations stored on the chip card, which are validated but which do not
contain any code sequences, can be sent to the device. The code
sequences must then be taught to the corresponding safety AS-i slaves.
This procedure is useful when you want to use a safety program in several
safety monitors without any changes.
3.
Using a chip card with complete configuration
In contrast to the master configuration, the complete configuration also con-
tains the code sequences for all included slaves. Sending the complete con-
figuration from the chip card to the Safety Monitor can make replacement of
the device enormously simpler and faster.
8.3.1
Description of configuration using ASIMON 3 G2 software
The following description represents a short guide to configuring the AS-i Safety
Monitor. For a detailed description of the
ASIMON 3 G2
software, refer to the cor-
responding manual for the
ASIMON 3 G2
configuration software.
The
ASIMON 3 G2
software is responsible for the following:
•
Configuring the AS-i Safety Monitor
•
Documenting the device configuration
•
Starting up the AS-i Safety Monitor
•
Diagnosing the AS-i Safety Monitor
Proceed as follows:
•
Install the program on your PC.
•
Apply power to the AS-i Safety Monitor
•
Connection of monitors with a RS 232 diagnostics interface
Information!
For additional information refer to section Description of configuration using chip card
with master configuration.
Information!
For additional information refer to Configuration using a chip card with complete confi-
guration.
Information!
The description of the
ASIMON 3 G2
program can be found in the separate software
manual.
Information!
To prevent ESD damage, we recommend grounding at an appropriate location before
plugging in the interface cable to the Safety Monitor.