AS-i Safety Monitor for 2 AS-i circuits
Operation in advanced display mode
9.4.4
FAULT DETECTOR
Main Menu || DIAGNOSIS ||
FAULT DETECTOR
||
The FAULT DETECTOR menu displays information about the AS-i detector and
allows you to delete the history of the AS-i Monitor. Also, the HELP section de-
scribes the abbreviations in full.
By selecting RESET you can delete the history of the AS-i Monitor.
The HISTORY section lists the fault messages which have occurred for the AS-i
Monitor since the last RESET.
The CURRENT section lists the current fault messages for the AS-i Monitor since
the last RESET.
The following fault messages are displayed:
•
Duplicate addressing (shows the 2 lowest slave addresses for which there is
duplicate addressing)
•
Earth faults
•
Noise
•
Overvoltage
FAULT DETECTOR
RESET
HISTORIC:
EFLT OVRV NOIS
ACTUAL:
EFLT OVRV NOIS
DUP ASI ADR:
0 | 31B
HELP:
EFLT EARTH FAULT
OVRV OVERVOLTAGE
NOIS NOISE
DUP ASI ADDR
DUPLICATE ASI
SLAVE ADDRESS
Information!
See also chapter Functions of the AS-i Fault Detector for further information.