Select
Configuration > Start-up
.
The dialog window
Start-up OIT system
will open. The current image will be
displayed in the left part of the dialog window. In the right side of the dialog
window in the area
Read mode
, the read mode can be switched to either direct
read or trigger read. If the trigger-read mode has been selected but the trigger is
missing, then the button
Normal position
will take you back to the start screen. A
complete read process can be run in the area
Automatic
. Here the number of
seconds after which a new read process is started can be set. Make sure that no
previously read or incorrectly read reads are sent to the PLC.
Figure 8.7
Dialog box
Commissioning OIT system...
Correct read errors: Repeat read operation
An instance may occur when the OIT system cannot read the data from a read-
only tag in a read operation through the PLC. In this case, the buttons
Manual
entry of ID/UID number(s)
and
Repeat read operation
will flash in the tool bar.
Proceed as follows in order to correct the read error by repeating a read operation:
1. Check possible causes of the error: Is the read-only tag correctly positioned in
the field of view of the camera (too close/too far to the lens/too tight in the field
of view of the camera)? Remove any obstacles that could interfere with proper
image taking. Check whether the lighting of the read-only tags is correct (too
bright/too dark) and provide sufficient contrast.
2. Click
or select
Process > Repeat read operation
.
The read operation is repeated.