HART Multiplexer System KFD*-HM*-16
Mounting and Installation
201
8-04
21
4.4.2
Supplying the Multiplexer Master with Power with Power Rail
You can use the Power Rail to supply the multiplexer master with 24 VDC. The supply is
provided using the KFA6-STR-1.24.500 power supply, for example.
Connecting the Multiplexer Master Power Supply
Connect the power supply via Power Rail.
Figure 4.6
Danger!
Danger to life from electric shock
Absent or insufficient insulation can result in electric shock.
Only connect supplies that provide protection against electric shock to power feed modules
(e. g. SELV or PELV).
Caution!
Property damage from use of isolators for Power Rail supply
Using the isolators for Power Rail supply can damage the isolators and make the Power Rail
fail.
Do not supply the Power Rail via isolators.
DIN mounting rail
24 V DC
1
2
3
4
5
6
7
8
19
17
13
18
16
20
14
21
15
KFD0-HMM-16
PWR
1
3
4
6
2
5
13
15
12
9
10
7
14
11
8
Power Rail
24 V DC
Summary of Contents for KFD Series
Page 1: ...ISO9001 3 HART Multiplexer System KFD HM 16 PROCESS AUTOMATION MANUAL ...
Page 50: ...2018 04 50 HART Multiplexer System KFD HM 16 Configuration Figure 6 10 Command caching window ...
Page 54: ...2018 04 54 HART Multiplexer System KFD HM 16 Configuration Figure 6 13 HART Scan wizard ...
Page 66: ...2018 04 66 HART Multiplexer System KFD HM 16 Operation Figure 7 1 Scan loops window ...
Page 89: ...HART Multiplexer System KFD HM 16 Notes 2018 04 89 ...
Page 90: ...2018 04 90 HART Multiplexer System KFD HM 16 Notes ...
Page 91: ...HART Multiplexer System KFD HM 16 Notes 2018 04 91 ...