2
018-
04
30
HART Multiplexer System KFD*-HM*-16
Commissioning
Factory Setting
5.2.3
LED Indication
The device is equipped with three LEDs which are located on the front of the housing.
The LEDs have the following meanings:
LED indication during the initialization process
LED indication during the scanning process
Faulty LED indication during commissioning
DIP switch 1
2
3
4
5
6
7
8
Meaning
Position
Off
Off
Off
Off
Off
Off
Off
Off
Manufacturer test disabled,
baud rate 9600 baud
RS-485 address 0
Table 5.4
Note!
In the factory setting, the address 0 is set. Ensure that you do not assign any addresses more
than once.
Color
Meaning
Red
Fault indication, detected during the initialization process
Green
Operating indication
Orange
HART communication with a field device
Table 5.5
Color
Status
Meaning
Red
Off
Initialization process
Green
Flashes
Orange
Off
Table 5.6
Color
Status
Meaning
Red
Off
Scanning process
Green
Lit
Orange
Flashes
Table 5.7
Note!
For further information about the scanning process, see chapter 5.2.4.
Color
Status
Meaning
Red
Flashes
If all three LEDs flash one after the other, DIP switch 1 (test) is in
the on position. Turn the switch to off and repeat commissioning.
Green
Flashes
Orange
Flashes
Table 5.8
Summary of Contents for KFD Series
Page 1: ...ISO9001 3 HART Multiplexer System KFD HM 16 PROCESS AUTOMATION MANUAL ...
Page 50: ...2018 04 50 HART Multiplexer System KFD HM 16 Configuration Figure 6 10 Command caching window ...
Page 54: ...2018 04 54 HART Multiplexer System KFD HM 16 Configuration Figure 6 13 HART Scan wizard ...
Page 66: ...2018 04 66 HART Multiplexer System KFD HM 16 Operation Figure 7 1 Scan loops window ...
Page 89: ...HART Multiplexer System KFD HM 16 Notes 2018 04 89 ...
Page 90: ...2018 04 90 HART Multiplexer System KFD HM 16 Notes ...