HART Multiplexer System KFD*-HM*-16
Configuration
201
8-04
47
6.7.3
Parameterizing Communication
Displaying Communication Parameters
1. Use the mouse to double-click the multiplexer master
KFD2-HMM-16
in
the project window.
2. In the editing window, open the
Configuration > Communication
menu.
The
Communication
window is displayed.
3. Click
Apply
to confirm your selection.
4. Select
Revert
to reset your selection.
The communication parameters between the host, HART multiplexer system, and field device
are displayed and set in the
Communication
menu:
Figure 6.8
Communication with the Multiplexer Master
In this case, the communication between the host and the HART multiplexer system
(HART communication 1) is described.
The
Communication to host HART master (as field device)
section displays the following
information about the device:
•
Address
: The RS-485 address of the multiplexer master is displayed here.
•
Unique identifier
: The unique, non-variable long address of the multiplexer master.
•
HART revision
: HART revision under which the multiplexer master is operated.
•
Minimum number of preambles
: Minimum number of preambles.
1
2
3
4
5
6
7
8
19
17
13
18
16
20
14
21
15
KFD0-HMM-16
Field devices
Host
Computer-based
maintenance station
or process control system
Data request
Cyclic data request
HART multiplexer system
Cache data
(Command caching)
HART communication 1
HART communication 2
Summary of Contents for KFD Series
Page 1: ...ISO9001 3 HART Multiplexer System KFD HM 16 PROCESS AUTOMATION MANUAL ...
Page 50: ...2018 04 50 HART Multiplexer System KFD HM 16 Configuration Figure 6 10 Command caching window ...
Page 54: ...2018 04 54 HART Multiplexer System KFD HM 16 Configuration Figure 6 13 HART Scan wizard ...
Page 66: ...2018 04 66 HART Multiplexer System KFD HM 16 Operation Figure 7 1 Scan loops window ...
Page 89: ...HART Multiplexer System KFD HM 16 Notes 2018 04 89 ...
Page 90: ...2018 04 90 HART Multiplexer System KFD HM 16 Notes ...
Page 91: ...HART Multiplexer System KFD HM 16 Notes 2018 04 91 ...