![Pepperl+Fuchs KFD Series Manual Download Page 77](http://html.mh-extra.com/html/pepperl-fuchs/kfd-series/kfd-series_manual_1527888077.webp)
HART Multiplexer System KFD*-HM*-16
Operation
201
8-04
77
Third Byte
Scan fault
The byte indicates an OR link for all the faults detected during the scanning process.
Example: If one field device is detected as
Disappeared
and another as
Mismatched
,
these two bits are set at the same time. The bit by bit coded information is shown in
the following table:
Bit
Status
Meaning
Action
7
Reserved
Reserved.
6
Searching
Field device is searched for due
to the
Disappeared
report.
• Check the cabling.
• Check the field device.
5
Disappeared
Field device is no longer
responding.
4
Appeared
Field device is responding
again.
Check the cabling.
3
Mismatched
Another field device has
responded instead.
Field device was replaced with
another field device. Check the
field device, rebuild
signal loops.
2 to 0
Reserved
Reserved.
Table 7.8
Note!
Additional information can be found in /1/, see chapter 9.3.
Summary of Contents for KFD Series
Page 1: ...ISO9001 3 HART Multiplexer System KFD HM 16 PROCESS AUTOMATION MANUAL ...
Page 50: ...2018 04 50 HART Multiplexer System KFD HM 16 Configuration Figure 6 10 Command caching window ...
Page 54: ...2018 04 54 HART Multiplexer System KFD HM 16 Configuration Figure 6 13 HART Scan wizard ...
Page 66: ...2018 04 66 HART Multiplexer System KFD HM 16 Operation Figure 7 1 Scan loops window ...
Page 89: ...HART Multiplexer System KFD HM 16 Notes 2018 04 89 ...
Page 90: ...2018 04 90 HART Multiplexer System KFD HM 16 Notes ...
Page 91: ...HART Multiplexer System KFD HM 16 Notes 2018 04 91 ...