HART Multiplexer System KFD*-HM*-16
Appendix
135
Read dynamic data from up
to 7 field devices.
For the specified extended addresses, the function returns
the following data:
• The specified scan command
• Extended address
• HART data
136
Read scan status of up to
31 field devices.
For the specified extended addresses, the function returns
the scan status of the field device (0 = deactivated,
1 = activated).
137
Write scan status of up to
31 field devices.
Set the scan status for the specified extended addresses
(0 = deactivated, 1 = activated).
138
Read fault overview of up to
27 field devices.
The fault overview provides an OR combination of
communication faults and status bits.
139
Delete fault overview of up to
35 field devices.
Fault overview is deleted.
140
Read the number of
command requests and
command faults from up to
16 field devices.
Communication statistics on received or bad messages
are returned.
141
Delete the number of
command requests and
command faults from up to
16 field devices.
Communication statistics are deleted.
142
Read all communications of
the multiplexer devices.
The communication statistics concerning
the multiplexer devices are returned.
143
Delete all communications of
the multiplexer devices.
The communication statistics concerning
the multiplexer devices are deleted.
144
Number of message repeats. • Repetitions in the event of
Busy
report: 0 to 11,
default setting is 0
• Repetitions in event of communication faults: 0 to 11,
default setting is 2
145
Write the number of
message repeats.
146
Read the specified
scan command.
During the scan, the HART commands 1, 2, or 3 can be
executed, see above.
147
Specify scan command.
148
Read scan status.
This reads or specifies the status of the scan function,
see chapter 7.3.3.
• 0: Scan function is deactivated, default setting after
a device reset.
• 1: Normal scan function is activated.
• 2: Special scan function is activated,
see command 158, 159.
149
Write scan status.
150
Read master type.
• 1 = Primary master, default setting
• 0 = Secondary master
151
Write master type.
152
Read loop search type.
The loop search type defines which polling address is used
to search for a device that has not responded after repeated
requests, (disappeared, see also command 129).
• 0: Single field device, 4 mA to 20 mA (single analog),
only polling address 0, default setting
• 1: Single field device, unknown (single unknown), first of
the polling addresses 0 to 15
1
• 2: Reserved for multidrop
153
Write loop search type.
Command
Action
Meaning
Summary of Contents for KFD Series
Page 1: ...ISO9001 3 HART Multiplexer System KFD HM 16 PROCESS AUTOMATION MANUAL ...
Page 50: ...2018 04 50 HART Multiplexer System KFD HM 16 Configuration Figure 6 10 Command caching window ...
Page 54: ...2018 04 54 HART Multiplexer System KFD HM 16 Configuration Figure 6 13 HART Scan wizard ...
Page 66: ...2018 04 66 HART Multiplexer System KFD HM 16 Operation Figure 7 1 Scan loops window ...
Page 89: ...HART Multiplexer System KFD HM 16 Notes 2018 04 89 ...
Page 90: ...2018 04 90 HART Multiplexer System KFD HM 16 Notes ...
Page 91: ...HART Multiplexer System KFD HM 16 Notes 2018 04 91 ...