HART Multiplexer System KFD*-HM*-16
Configuration
Communication with the Field Devices
In this case, the communication between the HART multiplexer system and the field devices
(HART communication 2) is described.
The
Communication to field devices (as HART master)
section displays the following
information. This information can be changed and saved by the user.
•
Master type
: 2 HART masters may be connected to a HART signal loop, whereby
the parameterization must differentiate between the primary master and the
secondary master. The setting at this point indicates whether the multiplexer master
addresses the field devices as primary or secondary HART master.
•
Retries on "Busy"
: Number of repeat attempts to establish communication
with the field device if the field device reports
Busy
.
•
Retries on error
: Number of repeat attempts to establish communication
with the field device if a fault occurs.
•
Loop scan address range
: This defines the address range in which the field devices on
the individual signal loops are searched for, see chapter 6.7.4:
•
Scan address 0 only
: The multiplexer master uses only address 0 to search for
connected devices.
•
Scan addresses 0 to 15
: The multiplexer master searches for all
polling addresses between 0 and 15 and identifies the first device to respond.
Figure 6.9
Communication window
Summary of Contents for KFD Series
Page 1: ...ISO9001 3 HART Multiplexer System KFD HM 16 PROCESS AUTOMATION MANUAL ...
Page 50: ...2018 04 50 HART Multiplexer System KFD HM 16 Configuration Figure 6 10 Command caching window ...
Page 54: ...2018 04 54 HART Multiplexer System KFD HM 16 Configuration Figure 6 13 HART Scan wizard ...
Page 66: ...2018 04 66 HART Multiplexer System KFD HM 16 Operation Figure 7 1 Scan loops window ...
Page 89: ...HART Multiplexer System KFD HM 16 Notes 2018 04 89 ...
Page 90: ...2018 04 90 HART Multiplexer System KFD HM 16 Notes ...
Page 91: ...HART Multiplexer System KFD HM 16 Notes 2018 04 91 ...