Temperature Multi-Input Device
Function Block Descriptions
32
LIM_NOTIFY
Maximum number of unconfirmed alert notification
messages allowed. Fuchs TI Mux supports a
maximum of 42.
33
CONTIRM_TIME
The minimum time between retries of alert reports.
Retries are not possible when parameter is set to 0.
34
WRITE_LOCK
If set, no writes from anywhere are allowed, except to
clear WRITE_LOCK. Block inputs will continue to be
updated.
35
UPDATE_EVT
This alert is generated by any change to the static data.
36
BLOCK_ALM
The block alarm is used for all configuration, hardware,
connection failure, or system problems in the block. The
cause of the alert is entered in the subcode field. The first
alert to become active will set the Active status in the
ALARM_STATE subcode.
37
ALARM_SUM
The current alert status, unacknowledged states,
unreported states, and disabled states of the alarms
associated with the function block.
38
ACK_OPTION
Selection of whether alarms associated with the function
block will be automatically acknowledged.
39
WRITE_PRI
Priority of the alarm generated by clearing the write lock.
40
WRITE_ALM
This alert is generated if the write lock parameter is
cleared.
41
ITK_VER
Major revision number of the interoperability test case
used to register the device with Fieldbus FOUNDATION.
42
SERIAL_NUM
Unit specific serial number to identify production and
release information. Set by manufacturer.
43
SW_REV
The software revision of the firmware within the device.
Table 7.1
Resource block parameter list
Rel.
Index
Parameter
Description