Temperature Multi-Input Device
Installation and Commissioning
2
017-
05
11
3
Installation and Commissioning
In the following section you find information on how to install and commission the multi-
input/output (MIO) device in your fieldbus topology.
3.1
Mounting and Dismounting
Mounting/Dismounting F2D0-TI-Ex8.*
F2D0-TI-Ex8.* is designed for panel (wall) mounting.
■
Select mounting material that is suitable for the sub-surface (the wall).
■
Ensure that the mounting material guarantees secure fastening.
■
To attach the device: use 2 fixing screws with a diameter of 6 mm.
■
To dismount the device: Undo the fixing screws and take the device off the wall.
Mounting/Dismounting RD0-TI-Ex8.*
RD0-TI-Ex8.* is designed for mounting on a 35 mm DIN rail in accordance with EN 50022.
Danger!
Danger to life from using damaged or repaired devices.
Using a defective or repaired device can compromise its function and its electrical safety.
■
Do not use a damaged or polluted device.
■
The device must not be repaired, changed or manipulated.
■
If there is a defect, always replace the device with an original device from Fuchs.
Danger!
Explosion hazard from damaged electronic components
Premature wear of electronic components in a device that was previously used in a general
electrical installation can cause sparks that can ignite the surrounding potentially explosive
atmosphere.
Never install devices that have already been operated in general electrical installations in
electrical installations used in combination with hazardous areas!